Plan Review Notes For Permit 06020143 |
Permit Number |
06020143 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-07 00:00:00 | DENIED | | | | 1) THE ASSEMBLY SUBMITTED FOR THE POLY | | GLASS MODIFIED SYSTEM PAGE 44 OF THE | | PRODUCT APPROVAL IS FOR USE UNDER A TILE | | ROOF WHEN THE DESIGN PRESSURE FOR THE | | TILE IS USED FOR UPLIFT. SELECT THE | | CORRECT TYPE OF APPLICATION FROM THE | | NOA. | | | | 2) IF THE DESIGN PRESSURE FOR THE | | ASSEMBLY THAT IS TO BE INSTALLED IS LESS | | THAN -89PSF, THEN ENHANCED FASTENING OF | | THE UNDERLYMENT WILL BE REQUIRED IF | | ALLOWED BY LIMITATIONS ( LIMITATION #9 | | DOES NOT ALLOW IT). LIMITATION #7 DOES | | ALLOW ENHANCED FASTENING IN ACCORDANCE | | WITH RAS 117, BUT THE CALCULATIONS MUST | | BE DONE BY AN ARCHITECT, ENGINEER OR | | REGISTERED ROOF CONSULTANT AND SIGNED | | AND SEALED CALCULATIONS ARE REQUIRED TO | | BE SUBMITTED BEFORE A PERMIT IS ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | | | | | |
|