Plan Review Notes
Plan Review Notes For Permit 06020143
Permit Number 06020143
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-09 00:00:00SECOND REVIEW
  
 1) SUBMIT THE SHEETS FROM THE POLYGLASS
 MODIFIED BITUMEN SYSTEM NOA THAT SPECIFY
 THE APPROVED ASSEMBLY THAT WILL BE
 INSTALLED. THE DESIGN PRESSURES FOR THE
 ASSEMBLY ARE LISTED ON THESE SHEETS.
  
 2) THIS NOA (#03-0130.08) FOR FL985-R1
 REQUIRES ENHANCED FASTENING CALCULATIONS
 USING RAS 117 TO BE PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
 READ LIMITATION #7 ON PAGE 45 ON NOA.
  
 3) IF LIMITATION #9 IS SPECIFIED AT THE
 DESIGN PRESSURE LISTED FOR THE ASSEMBLY
 THEN NO INCREASE IN PRESSURES ARE
 ALLOWED. SEE LIMITATION #9 ON PAGE 45 OF
 THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  