Plan Review Notes
Plan Review Notes For Permit 06020143
Permit Number 06020143
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-02 00:00:00DENIED
  
 1) THE DESIGN PRESSURE FROM THE NOA OF
 -45 PSF FOR THE MODIFIED ROOF SYSTEM
 ASSEMBLY DOES NOT MEET THE REQUIRED
 UPLIFT OF -89 PSF. LIMITATION #9 DOES
 NOT ALLOW FOR ENHANCED FASTENING TO
 INCREASE THE DESIGN PRESSURE.
  
 2) THE PRODUCT APPROVALS FOR THE GAF
 SHINGLES HAVE BEEN UPDATED TO THE 2004
 FBC ON THE STATE WEBSITE. SUBMIT THE
 UPDATED VERSIONS. FL183-R1 AND NOA
 04-0820.01.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  