2006-06-20 00:00:00 | ********* UNSAT 4TH REVIEW ********** |
| |
| ** PLEASE SEE NOTES FROM PREVIOUS |
| REVIEWS DATED 3/6/06,5/09/06 6/11/06 |
| |
| 1) NOTE: PLEASE SEE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1,.1.2, .1.3 ETC |
| 13-415.1.ABC.3, 13-415.1.AB.1 , |
| 13-415.2.ABC.1 ETC. |
| PLEASE SEE MISSING ENERGY CODE |
| COMPLIANCE FORMS (FORM C) 2004, SEE |
| ABOVE. |
| |
| |
| PLEASE SEE THAT DETAILS AND NOTES ADDED |
| TO PLANS ARE FROM THE 2001 FBC CHAPTER |
| 13. |
| PLEASE SEE THAT THE NOTES AND DESIGN DO |
| NOT APPLY AS THE DESIGN SHALL BE UNDER |
| THE 2004 FBC. PLEASE SEE THAT THE REST |
| OF THE PLANS AND DESIGN ARE ALREADY |
| UNDER THE 2004 FBC. |
| MAY NOT USE 2001 FBC FOR CHAPTER 13 AND |
| THE 2004 FOR ALL OTHER AREAS. |
| |
| 2) NOTE: PLEASE SEE ONLY COPY OF THE NEW |
| ELECTRICAL E-1 WAS SUBMITTED AND THE |
| E-2WHICH IS IN SETS WASFROM THE |
| PREVIOUS SETS WHICH STILL CONTAINS THE |
| OLD SEAL WHICH IS NOT ACCEPTABLE. PLEASE |
| SEE NOTE #4. |
| MIN OF TWO SETS ARE REQUIRED, SIGNED, |
| DATED AND SEALED BY SAID ARCHITECTS; AND |
| ENGINEER'S OF RECORD. |
| PLEASE ALSO SEE THAT ALL PLANS SHALL BE |
| CLEAR AND VISABLE WITH ALL INFORMATION. |
| PLEASE KNOW THAT PLANS CONTAIN MANY |
| HANDRAWN ITEMS WHICH ARE NOT EASILY READ |
| AND PLANS NEED TO BE RE-DONE. |
| PLEASE SEE FBC ADMIN SECT 106.1.3 |
| 106.1.2,106.3.5 ETC |
| |
| 3) NOTE: " IMPORTANT" |
| PLEASE SEE PREVIOUS REVIEW NOTES ALSO |
| REQUESTED THAT WHEN PLANS ARE SUBMITTED, |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ANY OF THE SHEETS WHICH ARE STAMPED BY A |
| TRADE AS "PASSED", THEN THOSE WILL STILL |
| REMAIN IN NEW SETS. ONLY ONE SET OF ALL |
| OLD/VOIDED REMOVED SHEETS SHALL BE |
| SUBMITTED FOR REFERENCE. |
| ** PLEASE KNOW, THIS WILL HELP TO |
| EXPEDITE THE PLAN REVIEW PROCESS AS WE |
| WILL NOT BE ABLE TO MAKE ALL SHEETS INTO |
| COMPLETE SETS AND COULDDELAY THE |
| PROJECT UNTIL THIS IS DONE. |
| |
| 4) NOTE: PLEASE SEE NOTE FROM 2ND REVIEW |
| WHEN PLANS CAME BACK SEALED WITH A SEAL |
| CONTAINING THE WORDING "CERTIFICATE" . |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001 WHICH CHANGED THE |
| REQUIREMENT IN FEB 04 TO REQUIRE THE |
| WORDING OF "LICENSE" IN SAID SEAL. |
| PLEASE KNOW, AN EXTENSION WAS GRANTED BY |
| THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEER'S TO THE DATE OF DEC 31, 2005. |
| PLEASE SEE THE SHEET E-2 IS STILL THE |
| OLD SHEET CONTAINING THE OLD SEAL. |
| |
| 5) NOTE: PLEASE PROVIDE UPDATED PLUMBING |
| SHEETS AS THE SHEETS IN SETS WHICH WERE |
| ALREADY STAMPED BY THE PLUMBING REVIEW |
| NOW CONTAIN "WHITE-OUT" AND HANDRAWN |
| CHANGES. PLEASE KNOW THESE SHEETS WHICH |
| WERE ALREADY STAMPED HAVE NOW BEEN |
| "VOIDED". PLEASE KNOW UNDER FS 481, 471 |
| NO "WHITE-OUT" IS PERMITTED ON PLANS IN |
| ANY MANNER. |
| |
| 6) NOTE: PLEASE KNOW BASED ON REPEAT |
| COMMENTS FOR CODE COMPLIANCE THREE OR |
| MORE TIMES FOR THE SAME CODE REQUIREMENT |
| A FEE HAS BEEN ASSESSED AS REQUIRED |
| UNDER FLORIDA STATUES 553.80(2)(B). |
| PLEASE SEE THAT THE FS REQUIRES THIS FEE |
| TO THE DESIGN PROFESSIONAL. |
| PLEASE KNOW THE FEE MUST BE PAID BEFORE |
| THE PLANS ARE RESUBMITTED FORNEXT |
| REVIEW. |
| THE AMOUNT OF $2203.20 IS NOW OWED. |
| ** PLEASE KNOW ONE COPY OF EACH OF ALL |
| OLD ELECTRICAL SHEETS ARE BEING RETAINED |
| BY THE BUILDING OFFICAL FOR FILE AS THE |
| BUILDING OFFICAL MAY SUBMIT FOR PEIR |
| REVIEW BY THE FBPE'S AND BOARD'S LEGAL |
| COUNSEL. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |