Plan Review Notes
Plan Review Notes For Permit 06011259
Permit Number 06011259
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-11 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE NOTES DATED 3/6/06
  
 PLEASE PROVIDE LIGHTING CONTROOLS AS
 REQUIRED UNDER THE 2004 FBC CHAPTER 13
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SPECIFY THE TIME SCHEDULING, THE
 LOCATION OF THE OVER RIDE DEVICES.
 PLEASE SEE A MAX OF 4HRS IS PERMITTED
 FOR MANUAL OVERIDES, AND 30MIN FOR OCC
 SENSORS.
 PLEASE SEE AREAS CONTAINING SEPARATE
 SPACES W/ FLR TO CEILING HEIGHT
 PARTITIONS WHICH REQUIRE CONTROL IN EACH
 AREA.
  
 2) NOTE: PLEASE SEE ALL INFORMATION ON
 PLANS SHALL BE CLEAR AND VISABLE.
 FBC 106.3 ADMIN SEC. AS ADOPTED BY THE
 CITY OF WEST PALM BEACH
  
 3) NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT THE NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved