Plan Review Notes
Plan Review Notes For Permit 06011259
Permit Number 06011259
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00DENIED;
 1.UNISEX TOILET ROOM IS REQUIRED TO BE
 HANDICAP. FBC-2004 CHAPTER 11 SEC.
 11-4.1.3(11). DOOR SWING SHALL COMPLY
 WITH SEC.11-4.22.2, DOOR SWING CANNOT
 ENTER THE CLEAR FLLOR SPACE OF A
 FIXTURE.
 2.SANITARY RISER DIAGRAM; AIR ADMITANCE
 VALVES CAN BE USED ONLY ON THE TOP 4
 FLOORS WITHOUT A RELIEF VENT FBC-2004
 PLUMBING SEC. 917.3.1.
 3.WATER RISER DIAGRAM; WATER HAMMER
 ARRESTORS ARE REQUIRED ON LOUNGE SINK,
 SEC 604.9. WATER HAMMER ARRESTORS, TO BE
 INSTALLED PER MANUFACTURE'S
 RECOMMENDATIONS, AS CLOSE TO THE SOURCE
 AS POSSIBLE.
 PLUMBING PLAN REVIEW BY;