2006-03-06 00:00:00 | ******UNSAT ******** |
| |
| ** PLEASE SEE COMMENTS BELOW AND |
| COMMENTS FROM OTHER TRADES DUE TO THE |
| CHANGE IN OCCUPANCY AS NOTED FOR MEETING |
| THE CURRENT CODES. |
| |
| |
| 1)NOTE: PLEASE HAVE PLANS REFERENCE THE |
| CURRENT CODES, 2003 NFPA-101, 2002 |
| NFPA-72, AND 2002 NFPA-70. |
| |
| 3)NOTE: PLEASE SEE RISER INDICATES 3/0'S |
| FOR 225A'S? PLEASE SEE 310.16, WHERE |
| 3/0'S ARE ONLY RATED FOR 200A'S. |
| |
| 4)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| EXISITNG ELECTRICAL PANELS/EQUIPMENT. |
| 215.5, 110.26,240.24,408.7 |
| |
| 5)NOTE: PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1& .2, CONTROL OF |
| LIGHTING. |
| 13-413.1ABC.1, VOLTAGE DROP, PROVIDE |
| INFORMATION. |
| 13-415.1AB.1 |
| PLEASE PROVIDE, SCHEDULING, CIRCUITING |
| ETC. |
| |
| 6)NOTE: PLEASE SEE LOAD CALCUALTIONS |
| WHICH SHOWS LOADS: 180A'S IS LESS THAN |
| 208A'S?? PLEASE SEE 208A SERVICE COULD |
| NOT BE LOCATED ON ANY PLANS/RISER. |
| (MISPRINT).? |
| |
| 7)NOTE: PLEASE PROVIDE A MORE SPECIFIC |
| DETAIL OF LOADS. |
| 215.5/220 |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. ONE SET OF |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERNECE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |