Plan Review Notes
Plan Review Notes For Permit 06011259
Permit Number 06011259
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-14 00:00:001) A DETAIL DRAWING OF THE NEW BATHROOM
 IS REQUIRED SHOWING ALL THE REQUIREMENTS
 FOR ACCESSIBILITY. SHOW THE DIMENTIONS
 FOR GRAB BARS, CLEAR FLOOR SPACE, TOILET
 PAPER HOLDER ETC.
 DOORS SHALL NOT SWING INTO THE FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 SEC.11-4.23.2
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE STATE THE DIMENTIONS OF ALL
 OPENINGS/PASS-THROUGH ON DRAWINGS.
  
 4) SUBMIT THE ELEVATION DRAWINGS FOR THE
 LOUNGE/RECEPTION OR
 ADMINISTRATION,REPAIR LAB AND ALL OTHER
 WORK AREAS SHOWING THE HEIGHT OF THE
 SINKS AND COUNTER TOPS ETC. OF THESE
 AREAS.SEE FBC SEC.11-7
  
 5) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS .
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 6)IS THIS BUSINESS ON THE FIRST OR
 SECOND FLOOR. IF IT IS LOCATED ON THE
 SECOND FLOOR INDICATE THE ACCESSIBILITY
 TO THE AREA FOR THE HANDI-CAP. IF
 ELEVATORS ARE PROVIDED,STATE THE SIZE
 OF THE DOOR OPENINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  