Plan Review Notes For Permit 06011224 |
Permit Number |
06011224 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-14 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT THE MANUFACTURERS | | SPECIFICATIONS FOR THE EQUIPMENT BEING | | INSTALLED. | | | | 2} IS THIS A REQUIRED OR OPTIONAL | | SYSTEM? | | | | 3} PLEASE SEE THE FEEDER FROM THE | | GENERATOR TO THE NEW PULL BOX ARE SHOWN | | AS 350 MCM, PLEASE CORRECT. | | | | 4} THE TRANSFER SWITCH MUST BE SERVICE | | RATED WITH A MAIN DISCONNECTING MEANS TO | | SHUT BOTH EMERGENCY AND NORMAL POWER | | FROM THE BUILDING BEING SERVED PER | | 230.70 AND 225.31. THESE MUST BE GROUPED | | PER 225.34 AND 230.72. | | | | 5} PROVIDE A CALCULATION FOR THE LOADS | | TO BE SERVED BY THE GENERATOR. NOTE THIS | | IS A 200 AMP GENERATOR SUPPLYING A 400 | | AMP SWITCH, SEE 702.5, ATTACHED. | | | | 702.5 CAPACITY AND RATING. | | AN OPTIONAL STANDBY SYSTEM SHALL HAVE | | ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE | | OPERATED AT ONE TIME. | | | | 6} PLEASE SHOW THE OTHER PANEL AND | | TRANSFORMER LOCATIONS LISTED ON THE | | PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|