2006-02-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE EQUIPMENT BEING
 INSTALLED.
  
 2} IS THIS A REQUIRED OR OPTIONAL
 SYSTEM?
  
 3} PLEASE SEE THE FEEDER FROM THE
 GENERATOR TO THE NEW PULL BOX ARE SHOWN
 AS 350 MCM, PLEASE CORRECT.
  
 4} THE TRANSFER SWITCH MUST BE SERVICE
 RATED WITH A MAIN DISCONNECTING MEANS TO
 SHUT BOTH EMERGENCY AND NORMAL POWER
 FROM THE BUILDING BEING SERVED PER
 230.70 AND 225.31. THESE MUST BE GROUPED
 PER 225.34 AND 230.72.
  
 5} PROVIDE A CALCULATION FOR THE LOADS
 TO BE SERVED BY THE GENERATOR. NOTE THIS
 IS A 200 AMP GENERATOR SUPPLYING A 400
 AMP SWITCH, SEE 702.5, ATTACHED.
  
 702.5 CAPACITY AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME.
  
 6} PLEASE SHOW THE OTHER PANEL AND
 TRANSFORMER LOCATIONS LISTED ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW