Notes |
Date |
Text |
2006-02-09 00:00:00 | | | THE VALUE ON THE APPLICATION MUST | | REFLECT THE TOTAL VALUE OF LABOR AND | | MATERIAL PER 108.3 FBC.( COST OF | | GENERATOR ,ATS,SLAB, ETC.) | | | | | | 1}INDICATE FEEDER FROM PANEL "N" TO ATS | | IN PANEL "N" SCHEDULE. THIS IS TO | | PREVENT AN INADVERTENT POWER UP OF THE | | GENERATOR PANEL, CURRENTLY LABLED "L", | | WHILE ATTEMTING TO DE-ENERGISE IT WITH | | THE BREAKER, AND RE ENERGIZING IT WITH | | THE GENERATOR. | | | | 2} SHOW PANEL "S" ON THE RISER PER 215.5 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | | | |
|