2007-01-30 11:59:21 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING; CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC-2004, CHAPTER 1, ADMINISTRATION; |
| FBC-2004 CHAPTER 11. |
| |
| THIS IS A TENANT BUILD OUT COMPLETE SET OF PLANS AND |
| SEPERATE PERMIT REQUIRED. |
| THE FOLLOWING CORECTIONS ARE REQUIRED FOR PLUMBING PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE |
| TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED |
| TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE |
| RESUBMITTAL PER FBC-2004 CHAPTER 1 SECTION 102.2.1. |
| |
| 2. SHEETS P-1 AND P-2 INDICATE AN ABOVE GROUNDGREASE |
| INTERCEPTOR IN THE BUILDING. PER CITY OF WEST PALM |
| BEACH CODE SECTION 90.124 (7) (B) GREASE INTERCEPTORS |
| (SEPERATORS, GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE |
| OF THE FOOD PREPERATION AREA WITH THE DISHWASHER |
| DISCHARGING VIA A SEPERATE LINE. (F) EACH INTERCEPTOR |
| SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE. |
| CLEANOUTS SHALL BE STEEL MANHOLE COVERS. NO FIBERGLASS |
| INTERCEPTORS SHALL BE INSTALLED. |
| NOTE: FOR THIS APPROVAL OR A WAIVER PLEASE CONTACT THE |
| FOLLOWING. |
| ENVIRONMENTAL COMPLIANCE MANAGER |
| LYNN MASSON (561) 822-2271 |
| FAX (561) 822-2279 |
| E-MAIL- [email protected] |
| |
| 3. SHEETS P-1 FLOOR PLAN DOES NOT REFECT THE SANITARY |
| RISER DIAGRAM AND SHEET P-2 SANITARY RISER DIAGRAM DOES |
| NOT REFECT THE FLOOR PLAN. PLEASE CORRELATE AND |
| RESUBMIT. PER FBC-2004 CHAPTER 1 SECTION 106.1, |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE. |
| |
| 4. SHEET P-2 GREASE RISER DIAGRAM MISSING FLOOR DRAIN |
| AND PER FBC-2004 PLUMBING, TABLE 403.1 A SERVICE SINK |
| REQUIRED. |
| NOTE: FLOOR DRAIN AND SERVICE SINK SHALL DRAIN INTO THE |
| GREASE INTERCEPTOR. |
| |
| 5. SHEET P-1 BATH ROOMS: ALL TOILET ROOMS SHALL BE |
| ACCESSIBLE: SUBMIT A FLOOR PLAN DETAIL AND AN ELEVATION |
| DETAIL SHOWING COMPLIANCE WITH FBC-2004 CHAPTER 11 |
| FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION, |
| SECTIONS 11-4.16, 11-4.19 AND 11-4.22 AND ALL |
| SUBSECTIONS. |
| |
| 6. SHEET P-2 WATER ISOMETRIC: PER FBC-2004 PLUMBING |
| SECTION 608 PROTECTION OF POTABLE WATER SUPPLY, PLEASE |
| INDICATEA RPZV BACKFLOW PREVENTER ON THE |
| RESUBMITTAL. |
| |
| 7. SHEET P-2 PLUMBING GENERAL NOTES: A} PLEASE CHANGE |
| NOTE #1 TO READ, ALL WORK SHALL BE DONE IN ACCORDANCE |
| WITH THE FBC-2004 AND WITH ALL APPLICABLE REGULATIONS. |
| B}PLEASE ADD TO NOTE #16, WATER HAMMER ARRESSTORS PER |
| FBC-2004 PLUMBING SECTION 604.9. |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 8. SHEET P-2 GAS ISOMETRIC: PER FBC-2004 FUEL GAS |
| SECTION 404.14.1 LIMITATIONS. PLASTIC PIPE SHALL BE |
| INSTALLED OUTSIDE UNDERGROUND ONLY. PLASTIC PIPE SHALL |
| NOT BE USED WITHIN OR UNDER ANY BUILDING OR SLAB OR BE |
| OPERATED AT PRESSURES GREATER THAN 100 PSIG FOR NATURAL |
| GAS OR 30 PSIG FOR LP GAS. |
| |
| 9. SHEET P-2 GAS ISOMETRIC: EMERGENCY HOOD SHUT DOWN |
| SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |