Plan Review Notes
Plan Review Notes For Permit 06011130
Permit Number 06011130
Review Stop P
Sequence Number 5
Notes
Date Text
2007-01-30 11:59:21REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING; CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC-2004, CHAPTER 1, ADMINISTRATION;
 FBC-2004 CHAPTER 11.
  
 THIS IS A TENANT BUILD OUT COMPLETE SET OF PLANS AND
 SEPERATE PERMIT REQUIRED.
 THE FOLLOWING CORECTIONS ARE REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE
 TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED
 TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE
 RESUBMITTAL PER FBC-2004 CHAPTER 1 SECTION 102.2.1.
  
 2. SHEETS P-1 AND P-2 INDICATE AN ABOVE GROUNDGREASE
 INTERCEPTOR IN THE BUILDING. PER CITY OF WEST PALM
 BEACH CODE SECTION 90.124 (7) (B) GREASE INTERCEPTORS
 (SEPERATORS, GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE
 OF THE FOOD PREPERATION AREA WITH THE DISHWASHER
 DISCHARGING VIA A SEPERATE LINE. (F) EACH INTERCEPTOR
 SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE.
 CLEANOUTS SHALL BE STEEL MANHOLE COVERS. NO FIBERGLASS
 INTERCEPTORS SHALL BE INSTALLED.
 NOTE: FOR THIS APPROVAL OR A WAIVER PLEASE CONTACT THE
 FOLLOWING.
 ENVIRONMENTAL COMPLIANCE MANAGER
 LYNN MASSON (561) 822-2271
 FAX (561) 822-2279
 E-MAIL- [email protected]
  
 3. SHEETS P-1 FLOOR PLAN DOES NOT REFECT THE SANITARY
 RISER DIAGRAM AND SHEET P-2 SANITARY RISER DIAGRAM DOES
 NOT REFECT THE FLOOR PLAN. PLEASE CORRELATE AND
 RESUBMIT. PER FBC-2004 CHAPTER 1 SECTION 106.1,
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE.
  
 4. SHEET P-2 GREASE RISER DIAGRAM MISSING FLOOR DRAIN
 AND PER FBC-2004 PLUMBING, TABLE 403.1 A SERVICE SINK
 REQUIRED.
 NOTE: FLOOR DRAIN AND SERVICE SINK SHALL DRAIN INTO THE
 GREASE INTERCEPTOR.
  
 5. SHEET P-1 BATH ROOMS: ALL TOILET ROOMS SHALL BE
 ACCESSIBLE: SUBMIT A FLOOR PLAN DETAIL AND AN ELEVATION
 DETAIL SHOWING COMPLIANCE WITH FBC-2004 CHAPTER 11
 FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION,
 SECTIONS 11-4.16, 11-4.19 AND 11-4.22 AND ALL
 SUBSECTIONS.
  
 6. SHEET P-2 WATER ISOMETRIC: PER FBC-2004 PLUMBING
 SECTION 608 PROTECTION OF POTABLE WATER SUPPLY, PLEASE
 INDICATEA RPZV BACKFLOW PREVENTER ON THE
 RESUBMITTAL.
  
 7. SHEET P-2 PLUMBING GENERAL NOTES: A} PLEASE CHANGE
 NOTE #1 TO READ, ALL WORK SHALL BE DONE IN ACCORDANCE
 WITH THE FBC-2004 AND WITH ALL APPLICABLE REGULATIONS.
 B}PLEASE ADD TO NOTE #16, WATER HAMMER ARRESSTORS PER
 FBC-2004 PLUMBING SECTION 604.9.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 8. SHEET P-2 GAS ISOMETRIC: PER FBC-2004 FUEL GAS
 SECTION 404.14.1 LIMITATIONS. PLASTIC PIPE SHALL BE
 INSTALLED OUTSIDE UNDERGROUND ONLY. PLASTIC PIPE SHALL
 NOT BE USED WITHIN OR UNDER ANY BUILDING OR SLAB OR BE
 OPERATED AT PRESSURES GREATER THAN 100 PSIG FOR NATURAL
 GAS OR 30 PSIG FOR LP GAS.
  
 9. SHEET P-2 GAS ISOMETRIC: EMERGENCY HOOD SHUT DOWN
 SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721