Plan Review Notes For Permit 06011130 |
Permit Number |
06011130 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-09-19 00:00:00 | *****UNSAT***** | | | | | | | | | | | | 1.) CLOUDED/BUBBLED AREA TOP LEFT CORNER | | OF SHEET A-200 SHOULD REFERENCE NFPA 101 | | INSTEAD OF NFPA 10. | | | | 2.) FIRE EXTINGUISHERS SHOULD ALL BE | | RATED 2A10BC, NOT CLASS A (RESIDENTIAL | | UNIT) OR CLASS B (MERCANTILE UNIT). | | | | 3.) SHOW/DISPLAY NUMERICAL ADDRESS FOR | | THE STRUCTURE ON SHEET S-205. AS PER | | WEST PALM BEACH CODE, SEC. 78-6(2) THE | | ADDRESS SHALL BE POSTED ON THAT PORTION | | OF THE STRUCTURE FRONTING OR FACING THE | | STREET OR ROADSIDE (SPRUCE AVENUE). AS | | A REMINDER, NUMBERS SHALL BE NO LESS | | THAN 6" IN HEIGHT AND 1" IN WIDTH WHICH | | CONTRAST AND ARE CLEARLY DISTINGUISHABLE | | FROM THE BACKGROUND. | | | | | | | | | | ALL OTHER CONCERNS/COMMENTS FROM | | PREVIOUS FIRE PLAN REVIEW(S) HAVE BEEN | | ADDRESSED AND/OR CORRECTED. | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|