Plan Review Notes
Plan Review Notes For Permit 06011130
Permit Number 06011130
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2006-09-19 00:00:00*****UNSAT*****
  
  
  
  
  
 1.) CLOUDED/BUBBLED AREA TOP LEFT CORNER
 OF SHEET A-200 SHOULD REFERENCE NFPA 101
 INSTEAD OF NFPA 10.
  
 2.) FIRE EXTINGUISHERS SHOULD ALL BE
 RATED 2A10BC, NOT CLASS A (RESIDENTIAL
 UNIT) OR CLASS B (MERCANTILE UNIT).
  
 3.) SHOW/DISPLAY NUMERICAL ADDRESS FOR
 THE STRUCTURE ON SHEET S-205. AS PER
 WEST PALM BEACH CODE, SEC. 78-6(2) THE
 ADDRESS SHALL BE POSTED ON THAT PORTION
 OF THE STRUCTURE FRONTING OR FACING THE
 STREET OR ROADSIDE (SPRUCE AVENUE). AS
 A REMINDER, NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH WHICH
 CONTRAST AND ARE CLEARLY DISTINGUISHABLE
 FROM THE BACKGROUND.
  
  
  
  
 ALL OTHER CONCERNS/COMMENTS FROM
 PREVIOUS FIRE PLAN REVIEW(S) HAVE BEEN
 ADDRESSED AND/OR CORRECTED.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722