Plan Review Notes For Permit 06011130
Permit Number 06011130
Review Stop ENG
Sequence Number 3
Notes
Date Text
2006-09-14 00:00:00 
  
 FAILED FOR FOLLOWING REASONS:
  
 1. ALBERT RODRIGUEZ OF DALIMA WROTE IN
 HIS LETTER OF 8/23/06 THAT " THE CIVIL
 ENGINEER HAS PROVIDED THE RESPONSE....."
 FOR COMMENT MADE BY AMINI ON 3/10/06 &
 COMMENTS MADE BY STEVE S. ON 6/22/06. I
 COULD NOT FIND YOUR RESPONSE ANY WHERE
 IN THE PACKAGES YOU SENT ON 9/13/06.
  
 MAY BE WE DID NOT PROVIDE YOU ENOUGH
 EXPLANATIONS.
  
 2. PLEASE SHOW POLLUTION PREVENTION SILT
 FENCE AROUND THE SITE.
  
 3. STORM WATER CAL.,PERVIOUS, IMPERVIOUS
 AREA CAL.,CRITERIA FOR RUNOFF CAL.,SHOW
 CALCULATION FOR DETERMING # OF
 EXFILTRATION TRENCHES, AFTER THAT WHAT
 KINDS OF CONTROL STUCTURES, &
 DETAILS,ETC.,
  
 4. DRAWINGS WITH DETAILS OF CITY OF WPB,
 STANDARDS, FOR DRIVEWAY,
 SIDEWALK,APPROACHES, PARKINGS, WITH ADA,
 DUMPSTER ENCLOSURE DETAILS, ETC.,
 TO EXPEDITE, PLEASE RESPOND EACH ITEM OF
 THE PARAGRAPHS IN YOUR LETTER TO
 ENGINEERING.
  
 5. PLEASE SHOW STORM/DRANAGE WATER,
 SEWERMAIN,WATER MAIN, CONNECTIONS TO
 MAINS, ETC.,
  
 6. UTILITY (45TH STREET) MUST REVIEW
 BEFORE WE APPROVE.
  
 7. PLEASE PROVIDE ALL CATCH BASINS,
 STORM/DRAINAGE OUTLETS/INLETS IN THE
 PROJECT SITE AREAS, TO DETERMINE THAT
 THE NEIGHBOURING AREAS DO NOT GET
 FLOODED.
  
 PLEASE RESPOND EACH ITEM OF THE
 PRAGRAPHS TO ENGINEERING TO EXPEDITE THE
 PERMITTING
  
 RASIK CHOKSHI 805-6723