2006-06-15 00:00:00PERMIT: 06011130
 ADD: 2037 SPRUCE AVE
 CONT:PLAN REVIEW
 "WEST PALM BEACH HOUSING
 AUTHORITY"
 TEL: (561)655-8530
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENET# 6 FROM THE PREVIOUS REVIEW,
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2)COMMENT# 12 FROM THE PREVIOUS REVIEW,
 REPORT IS A COPY NOT RAISED SEAL. FL BLD
 CODE 1804.2.2 QUESTIONABLE SOILS, WHERE
 THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) COMMENT# 16 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOF ASSEMBLIES
 C) STORM SHUTTERS
 ROOF ASSEMBLIES, HIGHLIGHT WHICH
 SUBSYSTEM THAT WILL BE USED, ALSO SEE IF
 REPORT WILL REQUIRE ENHANCED FASTENING
 LIMITATION# 7 OR 9.
  
 INDICATE WHERE STORM SHUTTERS WILL BE
 STORED?
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 4) COMMENT# 18 FROM THE LAST REVIEW,
 A200 & A500 DOOR WAY ND01 PLANS INDICATE
 THE USE OF (2) 2'-8" DOORS. SEE
 11-4.13.5 A MINIMUM OF 32" CLEAR WIDTH
 REQUIRED.
  
 5) A401 & S204 COMMENT# 30 FROM THE
 PREVIOUS REVIEW, PLANS INDICATE A
 CONCRETE DECK, PROVIDE STEEL SIZE AND
 LAYOUT FOR THE 2ND FLOOR CONCRETE DECK.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  