2006-04-01 00:00:00 | PAUL SCHMITZ |
| [email protected] |
| FBC 2004 PLUMBING CODE PLAN REVIEW |
| FBC2004 FUEL GAS CODEPLAN REVIEW |
| FBC 2004 CH 11, FL ACESSIBILITY CODE |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPT.1, ADMINISTRATION, 2004 EDITION |
| DENIED |
| |
| 1)NOTE: PLEASE BE SURE PLANS REFERENCE |
| CURRENT CODES IN EFFECT FOR THIS SCOPE |
| OF WORK. |
| PLEASE SEE COVER SHEET(S) WHICH |
| REFERENCE THE 2001 FBC? |
| PLEASE SEE OTHER SHEET REFLECT THE 2004. |
| PLEASE BE SURE PLANS ALSO REFERENCE THE |
| 2002 NFPA-72, 2003 NFPA-101, 2002 |
| NFPA-70 |
| |
| 2)NOTE: PLEASE SEE PLANS SUBMITTED ARE |
| NOT SIGNED, DATED OR SEALED BY ARCHITECT |
| OR ENGINEER;S OF RECORD. THIS IS NOT |
| REQUIRED WHEN SUBMITTING FOR"PLAN |
| REVIEW" , HOWEVER IS REQUIRED WHEN |
| SUBMITTING FOR PERMIT. |
| FS 481.221,471.025 |
| |
| 3)NOTE: PLEASE SEE MISSING FIRM LICENSE |
| NUMBER FOR ARCHITECTURAL FIRM. FLORIDA |
| ADMINISTRATIVE CODE, 61G1-16.004, FS |
| 481.219 |
| PLEASE KNOW, THIS IS REQUIRED ON ALL |
| SHEETS AND FOR ALL TRADES WHICH CONTAIN |
| THE TITLE BLOCK FOR ARCHITECTURAL FIRM. |
| THIS COMMENT STANDS FOR ALL REVIEWS |
| WHETHER OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 4) PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| 5) SHT P-201 |
| SEC 607.3 THERMAL EXPANSION CONTROL. |
| A MEANS OF CONTROLLING INCREASED |
| PRESSURE CAUSED BY THERMAL EXPANSION |
| SHALL BE PROVIDED WHERE REQUIRED IN |
| ACCORDANCE WITH SECTIONS 607.3.1 AND |
| 607.3.2. |
| |
| 6) PROTECTION OF POTABLE WATER SUPPLY |
| 608.1 GENERAL. |
| A POTABLE WATER SUPPLY SYSTEM SHALL BE |
| DESIGNED, INSTALLED AND MAINTAINED IN |
| SUCH A MANNER SO AS TO PREVENT |
| CONTAMINATION FROM NONPOTABLE LIQUIDS, |
| SOLIDS OR GASES BEING INTRODUCED INTO |
| THE POTABLE WATER SUPPLY THROUGH |
| CROSS-CONNECTIONS OR ANY OTHER PIPING |
| CONNECTIONS TO THE SYSTEM. BACKFLOW |
| PREVENTER APPLICATIONS SHALL CONFORM TO |
| TABLE 608.1, EXCEPT AS SPECIFICALLY |
| STATED IN SECTIONS 608.2 THROUGH |
| 608.16.9. |
| (RPZV REQUIRED ON WATER SERVICE) |
| |
| END OF COMMENTS, QUESTIONS 561-805-6692 |
| |
| |
| |
| |