Plan Review Notes For Permit 06011130 |
Permit Number |
06011130 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-21 00:00:00 | ******PLAN REVIEW ONLY****** | | | | ******DENIED****** | | | | 1) CIVIL DRAWINGS HAVE BEEN REQUESTED BY | | ENGINEERING PLAN REVIEW. IN ADDITION, | | PLEASE IDENTIFY THE CLOSEST FIRE HYDRANT | | TO THE BUILDING. | | | | 2) PLEASE CLARIFY THE NFPA SECTION ON | | SHT A-300. NFPA 101, 2003 EDITION SHALL | | BE REFERENCED. | | | | 3) AN ADDRESS IS REQUIRED ON BUILDING | | AND SHALL BE A MINIMUM OF 6" IN HEIGHT | | AND CONTRASTING TO THE BACKGROUND. | | | | 4) STAIRS TO COMPLY WITH FBC AND NFPA | | 101, CHAPTER 7. | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | 6) PLEASE INDICATE THE INTERIOR FINISH | | CLASSIFICATION OF WALLS AND CEILINGS. | | | | 7) CONSTRUCTION, ALTERATION AND | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLANS REVIEW (561) 805-6722 |
|