Plan Review Notes
Plan Review Notes For Permit 06011130
Permit Number 06011130
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-02 00:00:00********** UNSAT **********
  
 ** PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY NAD HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE BE SURE PLANS REFERENCE
 CURRENT CODES IN EFFECT FOR THIS SCOPE
 OF WORK.
 PLEASE SEE COVER SHEET(S) WHICH
 REFERENCE THE 2001 FBC?
 PLEASE SEE OTHER SHEET REFLECT THE 2004.
 PLEASE BE SURE PLANS ALSO REFERENCE THE
 2002 NFPA-72, 2003 NFPA-101, 2002
 NFPA-70
  
 2)NOTE: PLEASE SEE PLANS SUBMITTED ARE
 NOT SIGNED, DATED OR SEALED BY ARCHITECT
 OR ENGINEER;S OF RECORD. THIS IS NOT
 REQUIRED WHEN SUBMITTING FOR"PLAN
 REVIEW" , HOWEVER IS REQUIRED WHEN
 SUBMITTING FOR PERMIT.
 FS 481.221,471.025
  
 3)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER FOR ARCHITECTURAL FIRM. FLORIDA
 ADMINISTRATIVE CODE, 61G1-16.004, FS
 481.219
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHICH CONTAIN
 THE TITLE BLOCK FOR ARCHITECTURAL FIRM.
 THIS COMMENT STANDS FOR ALL REVIEWS
 WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 4)NOTE: PLEASE KNOW, CUNDUIT IN OPEN
 TENANT SPCE SHALL BE PROTECTED, BY BEING
 SCHEDULE 80 OF PVC OR RIGID METAL ETC.
 352,354,358
  
 5)NOTE: PLEASE SEE THAT THE ADDRESS OF
 JOB FOR SCOPE OF WORK WILL BE REQUIRED
 ON TITLE BLOCKS.
  
 6)NOTE: PLEASE SEE 2002 NEC, 210.12 AS
 ARC FAULT PROTECTION IS REQUIRED FOR ALL
 "OUTLETS" IN SLEEPING RMS.
 PLEASE SEE CIRCUIT(S), AS ONE BEDRM
 CIRCUIT DOES NOT INDICATE ARC FAULT
 PROTECTION, ALTHOUGH A CIRCUIT #16,
 DOES, YET THIS CIRCUIT COULD NOT BE
 LOCATED ON PLANS OR FOR CIRCUIT FOR
 BEDRMS?
 PLEASE CORRELATE.
  
 7)NOTE: PLEASE SEEMISSING FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. THE FOOTER STEELL IS REQUIRED
 PER NEC 250.50,250.52 AND THIS AHJ.
 THIS CONNECTION SHALL BE MADE.
  
 8)NOTE: PLEASE SEE MISSING SMOKE
 DETECTOR ON FIRST FLR LEADING TO THE FLR
 ABOVE PER NFPA-72 11.5.1.1 .
  
 9)NOTE: PLEASE SEE THAT A MIN OF 10FT
 CANDLES (108 LUX) IS REQUIRED UNDER
 NORMAL LIGHTING CONDITIONS FOR STAIR
 WAY, AND IS PERMITTED TO BE RATED DOWN
 TO 1 FT CANDLE MIN UNDER EM CONDITIONS.
 LS 1017.8.1.3,7.9.2.2
  
 10)NOTE: PLEASE BE SURE TO COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESITONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  