Plan Review Notes
Plan Review Notes For Permit 06011130
Permit Number 06011130
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011130
 ADD: 2037 SPRUCE AVE
 CONT:PLAN REVIEW
 "WEST PALM BEACH HOUSING
 AUTHORITY"
 TEL: (561)655-8530
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G16.003 ARCHITECTS
  
 2)DALIMA STUDIO ARCHITECTURE
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3A) FUAT ORNARLI P E STRUCTURAL
 ENGINEER:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 3B) LNI: LEONARDO NAVEIRAS INC.
 CONSULTING ENGINEER. 471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 5) SHEET A100 CORRECT ALL REFRENCES TO
 THE 2001 FBC TO THE 2004 FBC.
  
 6) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 8) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 11)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12) 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 13) FBC 13-400.3.ABC.3 FORMS ENERGY
 COMPLIANCE FORMS:FORMS REFERENCED IN
 TABLE 400.3.ABC.3 SHALL BE USED TO
 DEMONSTRATE CODE COMPLIANCE WITH THIS
 CHAPTER. CLIMATE ZONES ARE LISTED BY
 COUNTY AND CITY IN APPENDIX 13-A OF THIS
 CHAPTER.
  
 14)BEFORE A PERMIT TO CONSTRUCT CAN
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH CO.,THE PERMIT PLANS STAMPED
 BY THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. IF BUILDINGS ARE
 BEING DEMOLISHED FROM THIS SITE NOTE
 TAKE THE IMPACT FEE CREDIT FOR THE
 DEMOLISHED BUILDING.
  
 15)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED OR OPERABLE
 B) EXTERIOR DOORS GLAZED OR NOT
 C) COMPONENTS & CLADDING TRUSS ANCHORS
 D) ROOFING ASSEMBLIES
 E) STORM SHUTTERS IF WINDOWS DO NOT
 HAVE LARGE MISSLE TESTING.
  
 17) S202 WIND DESIGN, NOTE DESIGNED TO
 THE HIGH VELOCITY WIND ZONE REQUIRED IN
 DADE AND BROWARD BUT NOT PALM BEACH
 COUNTY.MISSING THE APPLICABLE ENCLOSURE
 CLASSIFICATIONS AND, IF DESIGNING WITH
 ASCE 7, INTERNAL PRESSURE COEFFICIENT
 1603.1.4(4).
  
 18) A200 THE FRONT DOOR ND01 IS
 INDICATED AS (2) 2'-6" DOORS:1008.1.1
 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING
 SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR
 WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR OPEN 90 DEGREES (1.57 RAD).
 WHERE THIS SECTION REQUIRES A MINIMUM
 CLEAR WIDTH OF 32 INCHES (813 MM) AND A
 DOOR OPENING INCLUDES TWO DOOR LEAVES
 WITHOUT A MULLION, ONE LEAF SHALL
 PROVIDE A CLEAR OPENING WIDTH OF 32
 INCHES (813 MM).
  
 19) A100 SCOPE OF WORK INDICATES THERE
 TOO BE TWO UTILITY STUB OUTS FOR 2
 ACCESSIBLE RESTROOMS. WILL THE RESTROOM
 WALLS BE PART OF THIS PERMIT? IF SO
 INDICATE ON PLAN.
  
 20A) PLANS A201 INDICATE A 1 HR RATED
 CEILING IN THE FUTURE MERCANTILE, FIRST
 FLOOR PROVIDE UL OR GYPSUM ASSOC NUMBER.
  
 20B) PLANS INDICATE MERCANTILE FUTURE
 A/C, AT THAT TIME THE FIRE RATED CEILING
 WILL REQUIRE FIRE DAMPERS WHEN THE DUCT
 PENETRATES THE CEILING.
  
 21) SITE PLAN
 21A) PROVIDE A DETAIL AS TO THE
 ACCESSIBLE ROUTE INTO THE FIRST FLOOR
 FOR THE HANDICAPPED, IT APPEARS THAT THE
 HANDICAPPED ACCESS AISLE RUNS DIRECTLY
 INTO A 1'-4" COLUMN.
  
 21B) THE SECOND FLOOR UNIT DECENDS TO A
 LANDING ON THE INTERIOR OF THE BUILDING
 BUT THE SITE PLAN DOESN'T INDICATE A
 LANDING ON THE EXTERIOR?
  
 22) THE SECOND FLOOR UNIT IS A R-2
 OCCUPANCY, THE MINIMUM DOORWAY FOR ND 03
 AND ND 04 IS 32" CLEAR 1008.1.1 PART OF
 A MEANS OD EGRESS.
  
 23) A402 STAIRWELL AND HANDRAIL, STAIRS
 WILL REQUIRE HANDRAILS ON BOTH WALLS,
 1009.11 HANDRAILS . STAIRWAYS SHALL HAVE
 HANDRAILS ON EACH SIDE. HANDRAILS SHALL
 BE ADEQUATE IN STRENGTH AND ATTACHMENT
 IN ACCORDANCE WITH SECTION 1607.7.
  
 24)A402 THE HANDRAIL AT THE BOTTOM OF
 THE STAIRWELL:1009.11.5 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD
 OR THE WALKING SURFACE OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 25) A401 & A402 NOTE# 11, WRONG CODE
 SECTION OUT OFTHE 2001 FBC.
  
 26) A3.00 NORTH ELEVATION, SECOND STORY
 OVER THE ALLOWABLE 10 % UNPROTECTED
 OPENINGS. FLOOR TO CEILING X LENGTH OF
 BUILDING = 374 SQ FT X 10%= 37.4 OF
 UNPROTECTED OPENINGS. SEE TABLE 704.8 &
 SECTION 704.8.
  
 27) S201 STAIRWELL, EXPLAIN THE 2X12
 LEDGER THE ENTIRE LENGTH OF THE
 STAIRWELL?
  
 28) S203 SECTION 1 & 2, THE SECOND STORY
 FLOOR SYSTEM IS MISSING THE FIRE STOP AT
 THE CEING LINE. NOTE OCCUPANCY
 SEPERATION TO BE 1 HR RATED!SECTION 711
 HORIZONTAL ASSEMBLIES,712.3.1.2
 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED
 BY AN APPROVED PENETRATION FIRESTOP
 SYSTEM INSTALLED AS TESTED IN ACCORDANCE
 WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL
 OF 0.01 INCH (2.49 PA) OF WATER AND
 SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF
 THE WALL PENETRATED.
 717.2 FIREBLOCKING.
 IN COMBUSTIBLE CONSTRUCTION,
 FIREBLOCKING SHALL BE INSTALLED TO CUT
 OFF CONCEALED DRAFT OPENINGS (BOTH
 VERTICAL AND HORIZONTAL) AND SHALL FORM
 AN EFFECTIVE BARRIER BETWEEN FLOORS,
 BETWEEN A TOP STORY AND A ROOF OR ATTIC
 SPACE. FIREBLOCKING SHALL BE INSTALLED
 IN THE LOCATIONS SPECIFIED IN SECTIONS
 717.2.2 THROUGH 717.2.7
  
 29) THE SAME SITUATION SECOND FLOOR
 CEILING/ ROOF ASSEMBLY IS MISSING FIRE
 BLOCKING AT THE CEILING LINE.717.2.7.
  
 30) S204 SECTION# 4, PROVIDE STEEL SIZE
 AND SPACING FOR 2ND FLOOR CONCRETE DECK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL (561)805-6715
  