2006-04-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06011130 |
| ADD: 2037 SPRUCE AVE |
| CONT:PLAN REVIEW |
| "WEST PALM BEACH HOUSING |
| AUTHORITY" |
| TEL: (561)655-8530 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G16.003 ARCHITECTS |
| |
| 2)DALIMA STUDIO ARCHITECTURE |
| 481.219 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING |
| ARCHITECTURAL SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| 3A) FUAT ORNARLI P E STRUCTURAL |
| ENGINEER: |
| PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| |
| 3B) LNI: LEONARDO NAVEIRAS INC. |
| CONSULTING ENGINEER. 471.023 F.S. |
| CERTIFICATE OF AUTHORIZATION.THE TITLE |
| BLOCK FOR ANY SHEET BEARING THE NAME OF |
| AN ENGINEER PRACTICING UNDER A |
| FICTITIOUS NAME, A CORPORATION, OR A |
| PARTNERSHIP, OFFERING ENGINEERING |
| SERVICES, SHALL INCLUDE THE CERTIFICATE |
| OF AUTHORIZATION NUMBER. |
| ADD THE NUMBER TO EACH SHEET.THIS MAY |
| BE ADDED BY HAND. |
| |
| 4) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 5) SHEET A100 CORRECT ALL REFRENCES TO |
| THE 2001 FBC TO THE 2004 FBC. |
| |
| 6) 106.3.3* PRODUCT APPROVALS- 2004 |
| THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITTING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 7) (2004 FBC) 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE & |
| EXTENT OF THE WORK PROPOSED & SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND REVELENT |
| LAWS, ORDINANCES, AND RULES AND |
| REGULATIONS AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| |
| 8) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS |
| CODE SHALL BE PERMORMED IN A MANNER SO |
| AS NOT TO ADVERSLY IMPACT THE CONDITION |
| OF ADJACENT PROPERTY, UNLESS SUCH |
| ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE |
| PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| LIMITED TO THE CONTROL OF DUST, NOISE, |
| WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| THE STORAGE OF CONSTRUCTION MATERIALS. |
| NEW CONSTRUCTION ACTIVITY SHALL NOT |
| ADVERSELY IMPACT HISTORICSURFACE WATER |
| DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, & MAY REQUIRE SPECIAL |
| DRAINAGE DESIGNCOMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED |
| SITES.ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENET, INCLUDING |
| ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN |
| EXCESS OF 800SQ FT OF PERMEABLE LAND |
| AREA ON ANY PARCELL SHALL AS A PERMIT |
| CONDITION, PROVIDE A PROFESSIONALY |
| PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATE FROM A |
| LICENSED ENGINEER SHALL BE SUBMITTED TO |
| THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 9) 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM |
| HIGHWINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |
| |
| 10) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| |
| 11)1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IN THE LOWER 60 FEET (18.3 M) IN |
| BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED |
| OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IS IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| AND 203 REFERENCED THEREIN AS FOLLOWS: |
| 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| FEET (9.1 M) OF GRADE SHALL MEET THE |
| REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE |
| TEST. |
| |
| 12) 1802.2.1 QUESTIONABLE SOIL. |
| WHERE THE SAFE-SUSTAINING POWER OF THE |
| SOIL IS IN DOUBT, OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT |
| SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE |
| PROVISIONS OF SECTIONS 1802.4 THROUGH |
| 1802.6 . |
| |
| 13) FBC 13-400.3.ABC.3 FORMS ENERGY |
| COMPLIANCE FORMS:FORMS REFERENCED IN |
| TABLE 400.3.ABC.3 SHALL BE USED TO |
| DEMONSTRATE CODE COMPLIANCE WITH THIS |
| CHAPTER. CLIMATE ZONES ARE LISTED BY |
| COUNTY AND CITY IN APPENDIX 13-A OF THIS |
| CHAPTER. |
| |
| 14)BEFORE A PERMIT TO CONSTRUCT CAN |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH CO.,THE PERMIT PLANS STAMPED |
| BY THEM AND THE RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. IF BUILDINGS ARE |
| BEING DEMOLISHED FROM THIS SITE NOTE |
| TAKE THE IMPACT FEE CREDIT FOR THE |
| DEMOLISHED BUILDING. |
| |
| 15)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 16) FL BLD CODE 1609.1.4: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS FIXED OR OPERABLE |
| B) EXTERIOR DOORS GLAZED OR NOT |
| C) COMPONENTS & CLADDING TRUSS ANCHORS |
| D) ROOFING ASSEMBLIES |
| E) STORM SHUTTERS IF WINDOWS DO NOT |
| HAVE LARGE MISSLE TESTING. |
| |
| 17) S202 WIND DESIGN, NOTE DESIGNED TO |
| THE HIGH VELOCITY WIND ZONE REQUIRED IN |
| DADE AND BROWARD BUT NOT PALM BEACH |
| COUNTY.MISSING THE APPLICABLE ENCLOSURE |
| CLASSIFICATIONS AND, IF DESIGNING WITH |
| ASCE 7, INTERNAL PRESSURE COEFFICIENT |
| 1603.1.4(4). |
| |
| 18) A200 THE FRONT DOOR ND01 IS |
| INDICATED AS (2) 2'-6" DOORS:1008.1.1 |
| SIZE OF DOORS. |
| THE MINIMUM WIDTH OF EACH DOOR OPENING |
| SHALL BE SUFFICIENT FOR THE OCCUPANT |
| LOAD THEREOF AND SHALL PROVIDE A CLEAR |
| WIDTH OF NOT LESS THAN 32 INCHES (813 |
| MM). CLEAR OPENINGS OF DOORWAYS WITH |
| SWINGING DOORS SHALL BE MEASURED BETWEEN |
| THE FACE OF THE DOOR AND THE STOP, WITH |
| THE DOOR OPEN 90 DEGREES (1.57 RAD). |
| WHERE THIS SECTION REQUIRES A MINIMUM |
| CLEAR WIDTH OF 32 INCHES (813 MM) AND A |
| DOOR OPENING INCLUDES TWO DOOR LEAVES |
| WITHOUT A MULLION, ONE LEAF SHALL |
| PROVIDE A CLEAR OPENING WIDTH OF 32 |
| INCHES (813 MM). |
| |
| 19) A100 SCOPE OF WORK INDICATES THERE |
| TOO BE TWO UTILITY STUB OUTS FOR 2 |
| ACCESSIBLE RESTROOMS. WILL THE RESTROOM |
| WALLS BE PART OF THIS PERMIT? IF SO |
| INDICATE ON PLAN. |
| |
| 20A) PLANS A201 INDICATE A 1 HR RATED |
| CEILING IN THE FUTURE MERCANTILE, FIRST |
| FLOOR PROVIDE UL OR GYPSUM ASSOC NUMBER. |
| |
| 20B) PLANS INDICATE MERCANTILE FUTURE |
| A/C, AT THAT TIME THE FIRE RATED CEILING |
| WILL REQUIRE FIRE DAMPERS WHEN THE DUCT |
| PENETRATES THE CEILING. |
| |
| 21) SITE PLAN |
| 21A) PROVIDE A DETAIL AS TO THE |
| ACCESSIBLE ROUTE INTO THE FIRST FLOOR |
| FOR THE HANDICAPPED, IT APPEARS THAT THE |
| HANDICAPPED ACCESS AISLE RUNS DIRECTLY |
| INTO A 1'-4" COLUMN. |
| |
| 21B) THE SECOND FLOOR UNIT DECENDS TO A |
| LANDING ON THE INTERIOR OF THE BUILDING |
| BUT THE SITE PLAN DOESN'T INDICATE A |
| LANDING ON THE EXTERIOR? |
| |
| 22) THE SECOND FLOOR UNIT IS A R-2 |
| OCCUPANCY, THE MINIMUM DOORWAY FOR ND 03 |
| AND ND 04 IS 32" CLEAR 1008.1.1 PART OF |
| A MEANS OD EGRESS. |
| |
| 23) A402 STAIRWELL AND HANDRAIL, STAIRS |
| WILL REQUIRE HANDRAILS ON BOTH WALLS, |
| 1009.11 HANDRAILS . STAIRWAYS SHALL HAVE |
| HANDRAILS ON EACH SIDE. HANDRAILS SHALL |
| BE ADEQUATE IN STRENGTH AND ATTACHMENT |
| IN ACCORDANCE WITH SECTION 1607.7. |
| |
| 24)A402 THE HANDRAIL AT THE BOTTOM OF |
| THE STAIRWELL:1009.11.5 HANDRAIL |
| EXTENSIONS. |
| HANDRAILS SHALL RETURN TO A WALL, GUARD |
| OR THE WALKING SURFACE OR SHALL BE |
| CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT STAIR FLIGHT. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE |
| HANDRAILS SHALL EXTEND HORIZONTALLY AT |
| LEAST 12 INCHES (305 MM) BEYOND THE TOP |
| RISER AND CONTINUE TO SLOPE FOR THE |
| DEPTH OF ONE TREAD BEYOND THE BOTTOM |
| RISER. |
| |
| 25) A401 & A402 NOTE# 11, WRONG CODE |
| SECTION OUT OFTHE 2001 FBC. |
| |
| 26) A3.00 NORTH ELEVATION, SECOND STORY |
| OVER THE ALLOWABLE 10 % UNPROTECTED |
| OPENINGS. FLOOR TO CEILING X LENGTH OF |
| BUILDING = 374 SQ FT X 10%= 37.4 OF |
| UNPROTECTED OPENINGS. SEE TABLE 704.8 & |
| SECTION 704.8. |
| |
| 27) S201 STAIRWELL, EXPLAIN THE 2X12 |
| LEDGER THE ENTIRE LENGTH OF THE |
| STAIRWELL? |
| |
| 28) S203 SECTION 1 & 2, THE SECOND STORY |
| FLOOR SYSTEM IS MISSING THE FIRE STOP AT |
| THE CEING LINE. NOTE OCCUPANCY |
| SEPERATION TO BE 1 HR RATED!SECTION 711 |
| HORIZONTAL ASSEMBLIES,712.3.1.2 |
| THROUGH-PENETRATION FIRESTOP SYSTEM. |
| THROUGH PENETRATIONS SHALL BE PROTECTED |
| BY AN APPROVED PENETRATION FIRESTOP |
| SYSTEM INSTALLED AS TESTED IN ACCORDANCE |
| WITH ASTM E 814 OR UL 1479, WITH A |
| MINIMUM POSITIVE PRESSURE DIFFERENTIAL |
| OF 0.01 INCH (2.49 PA) OF WATER AND |
| SHALL HAVE AN F RATING OF NOT LESS THAN |
| THE REQUIRED FIRE-RESISTANCE RATING OF |
| THE WALL PENETRATED. |
| 717.2 FIREBLOCKING. |
| IN COMBUSTIBLE CONSTRUCTION, |
| FIREBLOCKING SHALL BE INSTALLED TO CUT |
| OFF CONCEALED DRAFT OPENINGS (BOTH |
| VERTICAL AND HORIZONTAL) AND SHALL FORM |
| AN EFFECTIVE BARRIER BETWEEN FLOORS, |
| BETWEEN A TOP STORY AND A ROOF OR ATTIC |
| SPACE. FIREBLOCKING SHALL BE INSTALLED |
| IN THE LOCATIONS SPECIFIED IN SECTIONS |
| 717.2.2 THROUGH 717.2.7 |
| |
| 29) THE SAME SITUATION SECOND FLOOR |
| CEILING/ ROOF ASSEMBLY IS MISSING FIRE |
| BLOCKING AT THE CEILING LINE.717.2.7. |
| |
| 30) S204 SECTION# 4, PROVIDE STEEL SIZE |
| AND SPACING FOR 2ND FLOOR CONCRETE DECK. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL (561)805-6715 |
| |