Plan Review Notes
Plan Review Notes For Permit 06011123
Permit Number 06011123
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-03 19:19:48*** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE PREVIOUS TWO REVIEWS WHICH
 REQUESTED ENERGY CALCULATIONS, PERFORMANCE LIGHTING
 LEVELS.
 PLEASE SEE THE LIGHTING OVER RIDE DEVICES MUST BE
 LOCATED AT ENTRANCES OF INGRESS INTO THE BUILDING WHERE
 AN OCCUPANT MAY ENTER AFTER HOURS. PLEASE SEE THAT ANY
 MANUAL OVER RIDE DEVICE MUST BE READILY ACCESSIBLE.
 PLEASE SEE SOME MEANS FOR OVER RIDING LIGHTING AT ALL
 LOCATIONS OF ENTRANCE.
 PLEASE SEE SOME DEVICES ON PLANS SEEM TO BE SHOWN AS A
 STANDARD WALL SWITCH AS INDICATED ON SYMBOL LEGEND.
 PLEASE SEE PLANS MENTIONS A TIME CLOCK, HOWEVER IS THIS
 A ASTRONOMICAL TC?
  
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN THESE.
 PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 ETC
  
 2) NOTE: PLEASE SEE 210.12 FOR LOADS TO BE FIGURED AND
 SHOWN PER 220.12.
 PLEASE SEE THE MINIMUM VA PER FT SHALL BE FIGURED FOR
 SERVICE/FEEDERS.
 PREVIOUS TWO REVIEWS.
  
 3) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH MENTIONS
 ALL LIGHTING IS EXISTING. HOW IS THIS POSSIBLE WHEN
 THIS IS A NEW BUILD OUT?
  
 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE A NOTICE
 TO FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE THREE OR MORE TIMES FOR THE SAME
 COMMENTS.
 PLEASE SEE A FEE OF $1680.00 IS NOW ASSESSED AND WILL
 BE REQUIRED TO BE PAID BEFORE NEXT RE-SUBMITTAL.
 PLEASE KNOW THIS FEE MAY ALSO BE FOR ANY OTHER TRADE
 WHICH MAY HAVE THE SAME COMMENT THREE OR MORE TIMES.
 PLEASE SEE BUILDING REVIEW COMMENTS.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved