Date |
Text |
2007-02-03 19:19:48 | *** UNSAT 3RD REVIEW *** |
| |
| 1) NOTE: PLEASE SEE PREVIOUS TWO REVIEWS WHICH |
| REQUESTED ENERGY CALCULATIONS, PERFORMANCE LIGHTING |
| LEVELS. |
| PLEASE SEE THE LIGHTING OVER RIDE DEVICES MUST BE |
| LOCATED AT ENTRANCES OF INGRESS INTO THE BUILDING WHERE |
| AN OCCUPANT MAY ENTER AFTER HOURS. PLEASE SEE THAT ANY |
| MANUAL OVER RIDE DEVICE MUST BE READILY ACCESSIBLE. |
| PLEASE SEE SOME MEANS FOR OVER RIDING LIGHTING AT ALL |
| LOCATIONS OF ENTRANCE. |
| PLEASE SEE SOME DEVICES ON PLANS SEEM TO BE SHOWN AS A |
| STANDARD WALL SWITCH AS INDICATED ON SYMBOL LEGEND. |
| PLEASE SEE PLANS MENTIONS A TIME CLOCK, HOWEVER IS THIS |
| A ASTRONOMICAL TC? |
| |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN THESE. |
| PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 ETC |
| |
| 2) NOTE: PLEASE SEE 210.12 FOR LOADS TO BE FIGURED AND |
| SHOWN PER 220.12. |
| PLEASE SEE THE MINIMUM VA PER FT SHALL BE FIGURED FOR |
| SERVICE/FEEDERS. |
| PREVIOUS TWO REVIEWS. |
| |
| 3) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH MENTIONS |
| ALL LIGHTING IS EXISTING. HOW IS THIS POSSIBLE WHEN |
| THIS IS A NEW BUILD OUT? |
| |
| 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE A NOTICE |
| TO FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR |
| CODE COMPLIANCE THREE OR MORE TIMES FOR THE SAME |
| COMMENTS. |
| PLEASE SEE A FEE OF $1680.00 IS NOW ASSESSED AND WILL |
| BE REQUIRED TO BE PAID BEFORE NEXT RE-SUBMITTAL. |
| PLEASE KNOW THIS FEE MAY ALSO BE FOR ANY OTHER TRADE |
| WHICH MAY HAVE THE SAME COMMENT THREE OR MORE TIMES. |
| PLEASE SEE BUILDING REVIEW COMMENTS. |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |