2007-02-22 16:56:20BUILDING PLAN REVIEW
 PERMIT: 06011123
 ADD: 2100 45TH STREETSUITE???
 CONT: RALPH DELLA-PIETRA, INC
 TEL: (561)745-8555
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NEITHER THE PLANS NOR THE PERMIT APPLICATION
 INDICATE WHICH SUITE
 THE WORK WILL BE COMPLETED WITHIN? 106.1.2*
 ADMINISTRATIVE CODE,
 ADDITIONAL INFORMATION REQUIRED.
  
 4) DESIGN PARAMETERS
 4A) 2004 FBC CORRECT THE CODE SECTION
 4B) DESIGNED TO ASCE 7-98 CORRECT
  
 5) LS-1 INDICATES THIS IS A TYPE V-B PLEASE SHOW THE
 AREA INCREASES THAT WERE TAKEN FOR THIS STRIP MALL TO
 CLASSIFY THIS TENANT SPACE AS A
 TYPE V-B? NOTES INDICATE THAT THERE IS NO FIRE
 SPRINKLERS SO ONLY THE FRONTAGE INCREASE CAN BE TAKEN.
 SECTION 506.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  