Plan Review Notes For Permit 06011123 |
Permit Number |
06011123 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-10-14 13:27:52 | 1)PLEASE PROVIDE DUCTWORK SIZE AND GRILL SIZE WITH | | CFM ON PLANS. | | 2)PLESE REFER TO SECTION 606 FBC (M) 2004 SMOKE | | DETECTION SYSTEM CONTROL. | | 3)PLEASE REFER TO SECTION 606.4.1 SUPERVISION . 4) | | PLEASE PROVIDE DETAIL ON CURB TIEDOWN TO ROOF ON THE | | PLANS. | | 5)PLEASE PROVIDE RTU #1 & #2 TIEDOWN TO CURB ON THE | | PLANS. | | 6)PLEASE REFER TO SECTION 307 FBC (M) 2004 CONDENSATE | | DISPOSAL. | | 7)PLEASE REFER TO SECTION 307.2.3 AUXILIARY AND | | SECONDARY DRAIN SYSTEM. | | 8)PLEASE REFER TO TABLE 403.3 REQUIRED OUTDOOR | | VENTILATION. | | 9)PLEASE REFER TO NOTES PAGE A/C 1 AND UPDATE TO 2001 | | CODE. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732. |
|