2006-10-14 13:27:521)PLEASE PROVIDE DUCTWORK SIZE AND GRILL SIZE WITH
 CFM ON PLANS.
 2)PLESE REFER TO SECTION 606 FBC (M) 2004 SMOKE
 DETECTION SYSTEM CONTROL.
 3)PLEASE REFER TO SECTION 606.4.1 SUPERVISION . 4)
 PLEASE PROVIDE DETAIL ON CURB TIEDOWN TO ROOF ON THE
 PLANS.
 5)PLEASE PROVIDE RTU #1 & #2 TIEDOWN TO CURB ON THE
 PLANS.
 6)PLEASE REFER TO SECTION 307 FBC (M) 2004 CONDENSATE
 DISPOSAL.
 7)PLEASE REFER TO SECTION 307.2.3 AUXILIARY AND
 SECONDARY DRAIN SYSTEM.
 8)PLEASE REFER TO TABLE 403.3 REQUIRED OUTDOOR
 VENTILATION.
 9)PLEASE REFER TO NOTES PAGE A/C 1 AND UPDATE TO 2001
 CODE.