Plan Review Notes
Plan Review Notes For Permit 06011123
Permit Number 06011123
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-19 00:00:00********UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED, ALONG
 WIHT NEW COMMENTS BASED ON PLANS
 SUBMITTED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE BOTTOM.
  
 1)NOTE: OK.
  
 2)NOTE:OK, MOST CODES ADDED, HOWEVER
 PLEASE BE SURE THE ELECTRICAL PLANS ALSO
 STATE THE 2004 FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3)NOTE: OK.
  
 4)NOTE:NO, PLEASE VERIFY AS THE
 DISONNECT IS BEING NOTED AS BEING FUSED
 AND 10K IS NOT COMMEN FOR THE AIC
 RATINSGS FOR FUSES. PLEASE SEE NEW
 COMMENTS ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE AIC RATINGS
 FOR THE NEW FUSES FOR MAINS. 110.9,215.5
  
 5)NOTE: OK. SEE NEW NOTES.
  
 6)NOTE: NO, PLEASE SEE NO SYSTEM WAS
 SUBMITTED AND SHOWN AS REQUIRED. A TC
 NOTED FOR LTS, DOES NOT GIVE ALL
 INFORMATION AS NEEDED. PLEASE PROVIDE
 THE SYSTEM, SCHEDULING, ALL OVER-RIDES
 ETC. PLEASE SEE PLANS DO NOT INDICATE
 ANY OVER-RIDE DEVICES, MAX TIMES
 PERMITTED ON THE DEVICES WHICH MAY BE
 INSTALLED.
 PLEASE SEE TAKING THE SECTIONS OF THE
 CODE AND QUOTING THE CODE IS NOT
 ACCEPTABLE IN LEIU OF MIN DESIGNS
 REQUUIRED ON PLANS FOR THE TECHNICAL REQUIREMENTS.
 FBC 106.1, ADMIN SECT.
 NO ENERGY CALCULATIONS, NO LIGHTING
 POWER ALLOWANCES ETC.
 PLEASE SEE NOTES BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REWUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE SEE A WORST CASE CALCUALTION TO
 BE SHOWN FOR VOTLAGE DROP TO MEET THE
 MIN AS SET FORTH IN 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1 & .2 FOR
 INTERIOR LIGHTING SHUTOFF, SPACE
 LIGHTING CONTROLS REQUIRED.PLEASE
 PROVIDE SCHEDULING.
 PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR
 LTS, AND TYPE OF TIME CLOCK REQUIRED .
 PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1 FOR
 CALCULATIONS.
  
 7)NOTE: OK, HOWEVER SEE LOAD IS SHOWN
 BEING DIVIDED BY 208V? PLEASE SEETHIS IS
 A 120V CIRCUIT, PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE TH REQUIRED SIGN
 CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN
 CIORCUIT MAY NOT FEED OTHER AREAS.
  
 8)NOTE: OK, HOWEVER PLEASE SEE THESE
 LOADS DO NOT CORRELATE WITH THE CIRCUITS
 AND LOADS SHOWN ON PANEL SCHEDULES, AND
 THE LOADS ARE ALSO SHOWN AT 208V AND NOT
 120V.??
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY "SHOW" WINDOW
 LIGHTING IS BEING SHOWN AS SIGN
 CIRCUITS?
 PLEASE SEE 220.12
  
 9)NOTE:NO, PLEASE SEE NOTES ABOVE, AS
 THE LOADS WILL CHANGE AND THE LOADS
 SHOWN DO NOT INDICATE ALL CONTINOUS
 LOADS AT 125%.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS, AND SHOW ALL CONTINUOUS
 LOADS AT 125%.
 PLEASE CORRELATE KNOWN RECEPT LOADS WITH
 LOADS SHOWN ON PANEL SCHEDULE.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 10)NOTE: OK, AS THE SERVICE IS BEING
 SHOWN AS EXISTING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GROUNDING ELECTRODE
 SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52.
  
 11)NOTE: OK.
  
 ***** NEW NOTES ****
  
 12) NOTE: PLEASE CORRELATE RISER WHICH
 INDICATES 350A OCP AND LOAD NOTES
 MENTIONS FUSES @ 300A??
 106.1.2 FBC ADMIN SECT,
  
 13) NOTE: PLEASE SEE 700.12E AS THE EM/
 EXT LTS ARE REQUIRED TO BE FED FROM THE
 NORMAL BRANCH CIRCUITS FEEDING LOCAL
 LIGHTING.
  
 14) NOTE: PLEASE SEE THAT NEW ELECTRICAL
 PANEL LOCATION SHALL INDICATE THIS AA AN ELECTRICAL
 ROOM, NO STORAGE.
 110.26.240.24, 408.7 ETC.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS. THIS IS
 ONLY GIVEN ANOTICE AT THIS TIME.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  