 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 UNSAT
  
 1) SHT P-1 SHOW HOW THE REST ROOM
 FACILITIES LOCATED IN THE STORAGE AREA,
 WILL COMPLY WITH, ACCESSILLE ROUTE
 11-4.3 ACCESSIBLE ROUTE.
 11-4.3.1 GENERAL.
 ALL WALKS, HALLS, CORRIDORS, AISLES,
 SKYWALKS, TUNNELS, AND OTHER SPACES THAT
 ARE PART OF AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.3.
 11-4.3.2 LOCATION.
 (1) AT LEAST ONE ACCESSIBLE ROUTE WITHIN
 THE BOUNDARY OF THE SITE SHALL BE
 PROVIDED FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND
 ACCESSIBLE PASSENGER LOADING ZONES, AND
 PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE.
 THE ACCESSIBLE ROUTE SHALL, TO THE
 MAXIMUM EXTENT FEASIBLE, COINCIDE WITH
 THE ROUTE FOR THE GENERAL PUBLIC.
 (2) AT LEAST ONE ACCESSIBLE ROUTE SHALL
 CONNECT ACCESSIBLE BUILDINGS,
 FACILITIES, ELEMENTS, AND SPACES THAT
 ARE ON THE SAME SITE.
 11-4.3.3 WIDTH.
 THE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE
 ROUTE SHALL BE 36 INCHES (915 MM) EXCEPT
 AT DOORS (SEE SECTIONS 11-4.13.5 AND
 11-4.13.6). IF A PERSON IN A WHEELCHAIR
 MUST MAKE A TURN AROUND AN OBSTRUCTION,
 THE MINIMUM CLEAR WIDTH OF THE
 ACCESSIBLE ROUTE SHALL BE AS SHOWN IN
 FIGURE 11-7(A) AND FIGURE 11-7(B).
 2) SEC 608 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVIVCE,
 LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  