Plan Review Notes
Plan Review Notes For Permit 06011123
Permit Number 06011123
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-24 00:00:00******DENIED******
  
 1) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) LIFE SAFETY SHALL BE IN COMPLIANCE
 WITH NFPA 101, 2003 EDITION.
  
 3) SHT E-2 ILLUSTRATES FIRE ALARM
 DEVICES, AND SHT LS-1 INDICATES THAT
 THERE IS NO FIRE ALARM. PLEASE ADVISE
 AND MAKE APPROPRIATE CORRECTION.
  
 3) WILL THIS PROJECT HAVE IT'S OWN FIRE
 ALARM SYSTEM, OR WILL IT BE TIED INTO AN
 EXISTING SYSTEM. IF A SEPARATE PANEL IS
 INSTALLED, AND THE BUILDING IS FULLY
 FIRE SPRINKLERED, THE SYSTEM IS REQUIRED
 TO BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE. APPROPRIATE DOCUMENTATION WILL
 BE REQUIRED PRIOR TO OR AT THE TIME OF
 THE FIRE ALARM FINAL INSPECTION.
  
 4) SEPARATE SHOP DRAWINGS ARE REQUIRED
 FOR FIRE SPRINKLER AND OR FIRE ALARM
 SYSTEMS OR REMODEL.
  
 5) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 6) WHERE PROVIDED AND AS PART OF A FIRE
 ALARM SYSTEM, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  