Plan Review Notes
Plan Review Notes For Permit 06011123
Permit Number 06011123
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-02 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEE THE SEAL FOR ENGINEER
 STILL CONTAINS THE WORDING OF
 "CERTIFICATE". PLEASE KNOW, FAC
 61G1-16.001 WHICH REQUIRED THE WORDING
 IN ALL SEALS TO BE CHANGED TO "LICENSE"
 PLEASE KNOW THIS RULING BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS WAS
 PASSED ON FEB 5, 2004. AN EXTENSION WAS
 GRANTED TO THE DATE OF 12/31/05,
 WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO
 LONGER ACCEPTABLE WITH THE WORDING OF "CERTIFICATE".
 PLEASE OBTAIN NEW SEAL.
  
 2)NOTE: PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3)NOTE: PLEASE SEE PLANS MENTIONS THE
 2005 NEC.
  
 4)NOTE: PLEASE PROVIDE THE AIC RATINGS
 FOR THE NEW FUSES FOR MAINS. 110.9,215.5
  
 5)NOTE: PLEASE SHOW ALL PANEL AND
 SERVICE LOCATIONS. PLEASE VERIFY IF ALL
 MAINS FOR THE ENTIRE BLDG ARE GROUPED.
 230.72
 RISER SHOWS WHAT APPEARS TO BE A SINGLE
 METER EXISTING SERVICE WITH NEW MAIN
 ADDED?, IS THIS THE SERVICE FOR THE
 ENTIRE BLDG?
 PLEASE SHOW AND VERIFY THE ENTIRE
 SERVICE.
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REQUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE SEE A WORST CASE CALCULATION TO
 BE SHOWN FOR VOLTAGE DROP TO MEET THE
 MIN AS SET FORTH IN 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1 & .2 FOR
 INTERIOR LIGHTING SHUTOFF, SPACE
 LIGHTING CONTROLS REQUIRED.PLEASE
 PROVIDE SCHEDULING.
 PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR
 LTS, AND TYPE OF TIME CLOCK REQUIRED .
 PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1 FOR
 CALCULATIONS.
  
 7)NOTE: PLEASE INDICATE TH REQUIRED SIGN
 CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN
 CIRCUIT MAY NOT FEED OTHER AREAS.
  
 8)NOTE: PLEASE VERIFY "SHOW" WINDOW
 LIGHTING IS BEING SHOWN AS SIGN
 CIRCUITS?
 PLEASE SEE 220.12
  
 9)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS, AND SHOW ALL CONTINUOUS
 LOADS AT 125%.
 PLEASE CORRELATE KNOWN RECEPT LOADS WITH
 LOADS SHOWN ON PANEL SCHEDULE.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 10)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52.
  
 11)NOTE: PLEASE PROVIDE ROOM AND ARE
 DESIGNATIONS ON PLANS.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE COMPLETETLY REMOVED ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-01 00:00:00IN ELEC FOR REVIEW