Date |
Text |
2006-03-02 00:00:00 | ********UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE THE SEAL FOR ENGINEER |
| STILL CONTAINS THE WORDING OF |
| "CERTIFICATE". PLEASE KNOW, FAC |
| 61G1-16.001 WHICH REQUIRED THE WORDING |
| IN ALL SEALS TO BE CHANGED TO "LICENSE" |
| PLEASE KNOW THIS RULING BY THE FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS WAS |
| PASSED ON FEB 5, 2004. AN EXTENSION WAS |
| GRANTED TO THE DATE OF 12/31/05, |
| WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO |
| LONGER ACCEPTABLE WITH THE WORDING OF "CERTIFICATE". |
| PLEASE OBTAIN NEW SEAL. |
| |
| 2)NOTE: PLEASEBE SURE ALL CURRENT |
| CODES FOR THE FOLLOWING ARE REFERENCED |
| ON ELECTRICAL PLANS. |
| 2002 NFPA-70, 2003 NFPA-101, 2002 |
| NFPA-72. |
| PLEASE SEE SHEETSWHICH REFLECT THE |
| 2001 FBC. |
| PLEASEKNOW, THE STATE OF FLORIDA |
| ADOPTED THE 2004 FBC ON OCT 1ST, 2005 |
| |
| 3)NOTE: PLEASE SEE PLANS MENTIONS THE |
| 2005 NEC. |
| |
| 4)NOTE: PLEASE PROVIDE THE AIC RATINGS |
| FOR THE NEW FUSES FOR MAINS. 110.9,215.5 |
| |
| 5)NOTE: PLEASE SHOW ALL PANEL AND |
| SERVICE LOCATIONS. PLEASE VERIFY IF ALL |
| MAINS FOR THE ENTIRE BLDG ARE GROUPED. |
| 230.72 |
| RISER SHOWS WHAT APPEARS TO BE A SINGLE |
| METER EXISTING SERVICE WITH NEW MAIN |
| ADDED?, IS THIS THE SERVICE FOR THE |
| ENTIRE BLDG? |
| PLEASE SHOW AND VERIFY THE ENTIRE |
| SERVICE. |
| |
| 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR |
| THE NEW REQUIREMENTS FOR COMMERCIAL |
| BLDGS. |
| PLEASE SEE A WORST CASE CALCULATION TO |
| BE SHOWN FOR VOLTAGE DROP TO MEET THE |
| MIN AS SET FORTH IN 13-413.1ABC.1 |
| PLEASE SEE 13-415.1.ABC.1 & .2 FOR |
| INTERIOR LIGHTING SHUTOFF, SPACE |
| LIGHTING CONTROLS REQUIRED.PLEASE |
| PROVIDE SCHEDULING. |
| PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR |
| LTS, AND TYPE OF TIME CLOCK REQUIRED . |
| PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING. |
| PLEASE SEE 13-415.1.AB.1 FOR |
| CALCULATIONS. |
| |
| 7)NOTE: PLEASE INDICATE TH REQUIRED SIGN |
| CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN |
| CIRCUIT MAY NOT FEED OTHER AREAS. |
| |
| 8)NOTE: PLEASE VERIFY "SHOW" WINDOW |
| LIGHTING IS BEING SHOWN AS SIGN |
| CIRCUITS? |
| PLEASE SEE 220.12 |
| |
| 9)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| CALCULATIONS, AND SHOW ALL CONTINUOUS |
| LOADS AT 125%. |
| PLEASE CORRELATE KNOWN RECEPT LOADS WITH |
| LOADS SHOWN ON PANEL SCHEDULE. |
| 220.3,220.10,220.11,220.13,215.3,230.42 |
| ETC |
| |
| 10)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52. |
| |
| 11)NOTE: PLEASE PROVIDE ROOM AND ARE |
| DESIGNATIONS ON PLANS. |
| |
| ** PLEASE SEE ANY OTHER POSSIBLE |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| |
| ** PLEASE COMPLETETLY REMOVED ANY |
| OLD/VOIDED SHEETS FROM SETS AND ONLY |
| INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-03-01 00:00:00 | IN ELEC FOR REVIEW |