Plan Review Notes For Permit 06011121 |
Permit Number |
06011121 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-07-24 11:10:28 | *****DENIED***** | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1.THE NUMERICAL ADDRESS, INCLUDING THE SUITE NUMBER, | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | SHEET. | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | SHALL COMPLY WITH NFPA 241. | | | | 3.SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR THE | | FIRE SPRINKLER REMODEL. | | | | 4.PLEASE SHOW THE LOCATION OF REQUIRED 2A:10BC RATED | | FIRE EXTINGUISHER(S) THAT SHALL NOT EXCEED THE 75' | | TRAVEL DISTANCE. | | | | 5.IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|