Date |
Text |
2007-07-20 09:21:04 | |
| |
| WE ASKED EXPLANATION FOR COMMENTS FOR REV 2, DATED |
| 2/2/07. THE PERSON WHO RESPONDED COMMENTS FOR REV 2, |
| DID NOT MENTIONED HIS/HER NAME ON THE COMMENTS SHEET. |
| HE/SHE SAID "NO CHANGES" FROM PREVIOUS REVISION " THIS |
| IS A SHELL ONLY" |
| IF THIS PERMIT FOR A SHELL ONLY THENYOU STILL NEED TO |
| SHOW ON DRAWINGS THE POLLUTION PREVENTION |
| DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT |
| FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE |
| SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & |
| PARTICLES. |
| |
| |
| BUT WE NEED THE FOLLOWING INFORMATIONFOR THIS PROJECT |
| SITE IN ONE OF THE PERMITS YOU APPLIED(WHAT PERMIT # I |
| CAN FIND THE FOLLOWING INFO): |
| |
| 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). |
| PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR |
| NOI. |
| YOU CAN GET NOI INFO FROM |
| WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ |
| NOTICE OF INTENT DEP FORM 62-621.300(4)(B), |
| EFFECTIVE MAY 1, 2003 |
| 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER & |
| ITS ENCLOSURE & ITS DETAILSPER CITY OF WPB, LOCATION |
| MUST BE ACCESSIBLE FOR PICKUP TRUCK. |
| 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , |
| SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, |
| 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST |
| FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS. |
| PLEASE SHOW IN YOUR STORM WATER CALS. |
| 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST |
| MATCH WITH AREAS USED IN STORM WATER QUALITY |
| CALCULATIONS. |
| 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES |
| AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM |
| WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL |
| STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING |
| ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION |
| TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS |
| WITH 100% FILL OF STORM WATER ELEVATION? |
| 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND |
| YOUR SITE. |
| 7. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, A COPY OF |
| GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM |
| WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH |
| STREET. |
| 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION |
| DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT |
| FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE |
| SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & |
| PARTICLES. |
| 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH |
| STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 10. |
| PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS |
| THAT WERE APPROVED AT 45TH STREET IN JUNE 2007. |
| |
| PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| PERMITTING PROCESS |
| |
| RASIK CHOKSHI805-6723 |