2006-10-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 FROM PREVIOUS REVIEW: COMMENT NUMBER TO
 REMAIN THE SAME.
  
 9. SHT A-2 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SF AREA OF THE
 ROOF, WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE SF
 OF THE ROOF AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE, (IF ANY).
 ***RESPONSE NOTED, BUT CALCULATIONS
 INDICATE A TOTAL OF 2,545SF. SHT A-1
 INDICATES NEW RETAIL 2,640SF. ALSO NO
 INFORMATION FOR THE VERTICAL WALLS
 ADJACENT TO THE ROOF FROM THE OTHER
 SPACES IN THE BUILDING. NORTH ELEVATION
 ON SHT A-2 INDICATES THE TOP OF THE
 PARAPET TO BE 29'0", AND THE TOP OF THE
 PARAPET TO THE SOUTH IS 16'0". NO
 CONTRIBUTION FROM THE VERTICAL WALLS WAS
 INDICATED IN THE CALCULATIONS. ALSO
 PLEASE INDICATE THE ELEVATION FOR THE
 ROOF AT BOTH THE HIGH END AND THE LOW
 END TO VERIFY CALCULATIONS.
  