Plan Review Notes
Plan Review Notes For Permit 06011121
Permit Number 06011121
Review Stop B
Sequence Number 2
Notes
Date Text
2006-10-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011121
 ADD: 2100 45TH ST. SUITE#
 CONT: ITASCA CONSTRUCTION
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1A)2ND REQUEST, PLEASE PROVIDE WHAT
 SUITE NUMBER WORK WILL COVER UNDER THIS
 PERMIT ON THE PERMIT APPLICATION.
  
 1B) SHEET SP-1 INDICATES NOTES TO
 PROVIDE CURB CUTS AND HANDICAPPED CCESS
 AISLES ALONG FRONTAGE OF BUILDING, IS
 THIS ALSO COVERED UNDER THIS
 PERMIT?PLEASE PROVIDE THIS INFORMATION
 ON THE PERMIT APPLICATION UNDER
 DESCRIPTION OF WORK.
  
 1C) SHEET SP-1 ALSO INDICATES ALONG 45TH
 STREET THE DRIVE APPROACH FOR THIS
 PROPERTY BEING WIDENED, IS THIS WORK
 ALSO TO BE INCLUDED UNDER THIS PERMIT?
 PLEASE PROVIDE THIS INFORMATION ON THE
 PERMIT APPLICATION UNDER DESCRIPTION OF
 WORK
  
 2A) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2B) COMPLIED.
  
 3) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4)BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 5A) COMPLIED.
 5B) COMPLIED.
 5C) 2ND REQUEST, TYPE OF CONSTRUCTION AS
 DEFINED IN CHAPTER 6 AND TABLE 601.
 5D) OCCUPANT LOAD.
 5E) IF AN AUTOMATIC FIRE SPRINKLER
 SYSTEM IS PROVIDED?
 5F) IF AN AUTOMATIC FIRE SPRINKLER
 SYSTEM IS REQUIRED?
 5G) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PRODUCT APPROVALS
 A) PANEL WALL COMPLIED.
 B) MULLIONS, COMPLIED.
 C) GLAZED SWING DOORS, COMPLIED
 D) HOLLOW METAL DOORS, COMPLIED.
 E) STORM SHUTTERS, COMPLIED.
 F) ROOFING ASSEMBLIES:
 SHEET 21 OF NOA, SUBSYSTEM IS NOT
 HIGHLIGHTED, SEE GENERAL LIMITATION# 7
 FOR LOW PSF.ENHANCED FASTENING ALLOWED
 PROVIDE CALCULATIONS FOR ENHANCED
 FASTENING AS PER RAS 117.
  
 10) COMPLIED.
  
 11A) COMPLIED.
 11B) COMPLIED.
 11C)
  
 12) 2ND REQUEST, EXISTING BUILDING CODE
 2004, 902.2 THE QUESTION 5C IS BASICALLY
 THE SAME QUESTION, WHAT IS THE MINIMUM
 BUILDING TYPE, WITH AREA INCREASES,
 FRONTAGE, AND OR FIRE SPRINKLERS?
 AREA LIMITATION. NO ADDITION SHALL
 INCREASE THE AREA OF AN EXISTING
 BUILDING BEYOND THAT PERMITTED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5.
  
 13) 2ND REQUEST13-101.1.2 ADDITIONS.
 ADDITIONS TO EXISTING COMMERCIAL
 BUILDINGS ARE CONSIDERED NEW BUILDING
 CONSTRUCTION AND SHALL COMPLY WITH
 SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED
 IN SECTION 101.1.1 .
 ADDITIONS TO EXISTING NONRESIDENTIAL
 BUILDINGS THAT ARE UNABLE TO COMPLY WITH
 CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE
 ENTIRE BUILDING INTO COMPLIANCE WITH THE REQUIREMENTS
 FOR NEW BUILDINGS.
  
 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL,
 WHEN APPLICABLE (SEE SECTION 202 ),
 COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400 C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED.
 SHELL BUILDING . A COMMERCIAL BUILDING
 THAT IS PERMITTED PRIOR TO DESIGN
 COMPLETION OR WHICH WILL BE FINISHED IN
 SECTIONS AT A TIME AFTER CONSTRUCTION OF
 THE SHELL.
  
 SHELL
 13-400.2.A.2 SHELL BUILDINGS.
 SHELL BUILDINGS SHALL COMPLY WITH THIS
 CODE BY METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED
 DESIGN PARAMETERS ARE
 KNOWN, A METHOD A CALCULATION MAY BE
 RESUBMITTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026