Date |
Text |
2006-05-04 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A-1 SHOW THE LOCATION OF THE |
| TOILET ROOM ON THE FLOOR PLAN. SECTION |
| 106.1.1. |
| |
| 2. SHT A-1 MINIMUM WIDTH FOR A HDCP |
| TOILET ROOM IS 5'3" FINISHED. PLANS SHOW |
| 5'2-1/2".SECTION 11-4.19.3, FIG. 28, |
| AND SECTION 405.3.1. |
| |
| 3. SHT A-1 A DRINKING FOUNTAIN IS |
| REQUIRED PER TABLE 403.1. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.15 AND ALL SUBSECTIONS. ALSO SHOW |
| COMPLIANCE WITH SECTION 11-4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| BENDING OR STOOPING. |
| |
| 4. SHT A-1 DETAIL 1/A-1 SHOW THE CLEAR |
| FLOOR SPACE FOR THE W/C PER SECTION |
| 11-4.16.2. |
| |
| 5. SHT A-1 DETAIL A/A-1 SHOW THE FLUSH |
| CONTROL PER SECTION 11-4.16.5. |
| |
| 6. SHT A-1 DETAIL A/A-1 INDICATE FAUCET |
| TYPE PER SECTION 11-4.19.5. |
| |
| 7. SUBMIT A SANITARY RISER ISOMETRIC |
| DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, AND |
| VENTS. SECTION 106.3.5.1.3. |
| |
| 8. SUBMIT A WATER RISER ISOMETRIC RISER |
| DIAGRAM. SHOW ALL PIPE SIZES, VALVES, |
| AND INDICATE AN RPZV BACKFLOW REQUIRED |
| ON THE WATER SERVICE TO SPACE. SECTIONS 106.3.5.1.3 AND |
| 608.13.2. |
| |
| 9. SHT A-2 SUBMIT CALCULATIONS FOR THE |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SECTION 1106 & 1107 WITH ALL |
| SUBSECTIONS. SHOW THE SF AREA OF THE |
| ROOF, WITH 1/2 AREA OF ALL VERTICAL |
| WALLS INCLUDING PARAPETS ADDED TO THE SF |
| OF THE ROOF AS WELL AS THE AREA OF ALL |
| ROOFS THAT DRAIN ONTO THE ROOF FROM |
| ABOVE, (IF ANY). |
| |
| 10. SHOW THE LOCATION OF ALL SECONDARY |
| ROOF DRAINS REQUIRED IN SECTION 1107.1 & |
| 1107.2. SEPARATE SYSTEMS REQUIRED. IF |
| THE SECONDARY ROOF DRAINS ARE EMERGENCY |
| OVERFLOW SCUPPERS, THEN THEY WILL BE |
| SIZED PER SECTIONS 1101.7, 1107.3 AND |
| TABLE 1106.7. THE SIZING OF THE OVERFLOW |
| SCUPPERS CAN NOT BE DETERMINED WITHOUT |
| REFERENCE TO THE DEFLECTION OF THE ROOF. |
| PLEASE STATE ON THE PLANS THAT THE |
| OVERFLOW SCUPPER SIZES COMPLY WITH |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. |
| |
| 11. SUBMIT DETAILS FOR THE DOWNSPOUTS, |
| COLLECTION HEAD, DRAIN SCUPPERS, & |
| EMERGENCY OVERFLOW SCUPPERS. SHOW THE |
| LENGTH, WIDTH, HEIGHT, OF EACH, AND SHOW |
| THE DISTANCE FROM THE ROOF TO THE FLOW |
| LEVEL OF THE EMERGENCY SCUPPER PER |
| SECTION 1503.4.3. INDICATE THE |
| TERMINATION POINT OF THE DOWNSPOUTS AND |
| SHOW COMPLIANCE WITHE SECTION 1503.6 |
| 1503.6 PROTECTION AGAINST DECAY AND |
| TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS |
| SHALL DISCHARGE AT LEAST 1 FOOT (305 MM) |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL |
| EXTENSIONS, OR SPLASH BLOCKS. GUTTERS |
| WITH DOWNSPOUTS ARE REQUIRED ON ALL |
| BUILDINGS WITH EAVES OF LESS THAN 6 |
| INCHES (152 MM) HORIZONTAL PROJECTION |
| EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| ABOVE ANOTHER ROOF. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| WHEN RESUBMITTING FOR REVIEW, PLEASE |
| SUBMIT ONE SET OF ORIGINAL SHEETS FOR |
| COMPARISON. |
| |