Plan Review Notes
Plan Review Notes For Permit 06011121
Permit Number 06011121
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 SHOW THE LOCATION OF THE
 TOILET ROOM ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 2. SHT A-1 MINIMUM WIDTH FOR A HDCP
 TOILET ROOM IS 5'3" FINISHED. PLANS SHOW
 5'2-1/2".SECTION 11-4.19.3, FIG. 28,
 AND SECTION 405.3.1.
  
 3. SHT A-1 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS. ALSO SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
  
 4. SHT A-1 DETAIL 1/A-1 SHOW THE CLEAR
 FLOOR SPACE FOR THE W/C PER SECTION
 11-4.16.2.
  
 5. SHT A-1 DETAIL A/A-1 SHOW THE FLUSH
 CONTROL PER SECTION 11-4.16.5.
  
 6. SHT A-1 DETAIL A/A-1 INDICATE FAUCET
 TYPE PER SECTION 11-4.19.5.
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, AND
 VENTS. SECTION 106.3.5.1.3.
  
 8. SUBMIT A WATER RISER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND INDICATE AN RPZV BACKFLOW REQUIRED
 ON THE WATER SERVICE TO SPACE. SECTIONS 106.3.5.1.3 AND
 608.13.2.
  
 9. SHT A-2 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SF AREA OF THE
 ROOF, WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE SF
 OF THE ROOF AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE, (IF ANY).
  
 10. SHOW THE LOCATION OF ALL SECONDARY
 ROOF DRAINS REQUIRED IN SECTION 1107.1 &
 1107.2. SEPARATE SYSTEMS REQUIRED. IF
 THE SECONDARY ROOF DRAINS ARE EMERGENCY
 OVERFLOW SCUPPERS, THEN THEY WILL BE
 SIZED PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE OVERFLOW
 SCUPPERS CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE STATE ON THE PLANS THAT THE
 OVERFLOW SCUPPER SIZES COMPLY WITH
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7.
  
 11. SUBMIT DETAILS FOR THE DOWNSPOUTS,
 COLLECTION HEAD, DRAIN SCUPPERS, &
 EMERGENCY OVERFLOW SCUPPERS. SHOW THE
 LENGTH, WIDTH, HEIGHT, OF EACH, AND SHOW
 THE DISTANCE FROM THE ROOF TO THE FLOW
 LEVEL OF THE EMERGENCY SCUPPER PER
 SECTION 1503.4.3. INDICATE THE
 TERMINATION POINT OF THE DOWNSPOUTS AND
 SHOW COMPLIANCE WITHE SECTION 1503.6
 1503.6 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. GUTTERS
 WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES (152 MM) HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 WHEN RESUBMITTING FOR REVIEW, PLEASE
 SUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]