Plan Review Notes
Plan Review Notes For Permit 06011121
Permit Number 06011121
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-06 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEEBLDG REVIEW NOTES
 FOR "S" SHEETS. PLEASE SEE THE SEAL FOR
 ENGINEERCONTAINS THE WORDING OF
 "CERTIFICATE". PLEASE KNOW, FAC
 61G1-16.001 WHICH REQUIRED THE WORDING
 IN ALL SEALS TO BE CHANGED TO "LICENSE"
 PLEASE KNOW THIS RULING BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS WAS
 PASSED ON FEB 5, 2004. AN EXTENSION WAS
 GRANTED TO THE DATE OF 12/31/05,
 WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO
 LONDER ACCEPTABLE WITH THE WORDING OF
 "CERTIFICATE".
 PLEASE OBTAIN NEW SEAL.
  
 2)NOTE: PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3A)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NUMBER ON "S" SHEETS,
 THIS WILL ALSO BE IN BLDG REVIEW NOTES.
 FS 471.023, FAC 61G15-23.002.
  
 3B) PLEASE SEE IN TWO SETS SHEET "S-1"
 IS SIGNED BY THE ARCHITECT AND ENGINEER
 ON THE SAME SEAL. (THIS SEEMS TO HAVE
 DONE IN ERROR) PLEASE CORRECT.
  
 4)NOTE: PLEASE KNOW, AN ELECTRICAL
 PERMIT /APPLICATION IS REQUIRED FOR
 ELECTRICAL DEMO WORK.
  
 5)NOTE: PLEASE NOTE: THESE PLANS DO NOT
 SEEM TO CORRELATE WITH TENANT FIT UP
 PLANS. PLEASE SEEE THE MAIN ELECTRICAL
 ROOM IS NOT SHOWN, WHICH SEEMS TO BE IN
 PART OF THIS LAYOUT??
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REWUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE PROVIDE ALL PRESCRITIVE
 CALCULATIONS FOPR ENCLOSING NEW AREA.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE COMPLETETLY REMOVED ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]