Plan Review Notes For Permit 06011059 |
Permit Number |
06011059 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-10-31 09:25:54 | PROVISO: | | | | EXHAUST FROM THE GENERATOR SHALL NOT BE LOCATED WITHIN | | 10 FT OF ANY DOOR, WINDOW, OR FRESH AIR INTAKE PER 2004 | | FMC 401.5.1. EXHAUST SHALL BE TERMINATE IN SUCH A | | MANNER AS NOT TO BE READILY DRAWN IN BY THE VENTILATING | | SYSTEM PER 2004 FMC 501.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected] | 2006-10-31 08:49:10 | | | | | |
|