2006-10-25 11:11:43GENERATOR NUETRAL AND GROUNDING ATTACHMENT AT UNIT
 SHALL BE VERIFIED.
 IT HAS BECOME THE ATTENTION OF THIS OFFICE THAT THERE
 ARE MANUFACTURE WHICH BUILD AND SHIP UNITSWIRED FOR
 "SEPARATELY DERIVED" UNITS. THIS MUST BE VERIFIED AS
 SYSTEM IS BEING SHOWN AS NOT SD.
 REVISE IF NEEDED.