2006-06-29 00:00:00********** UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE THE FOLLOWING NOTES AS ALL
 INFORMATION NEEDED WAS NOT SUBMITTED.
  
 ** PLEASE SEE SOME OF THE SAME NOTES
 FROM PREVIOUS REVIEW STILL APPLY.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1)NOTE: OK
  
 2)NOTE: OK.
  
 3)NOTE: NO, PLEASE SEE AN OLD SITE PLAN
 WAS SUBMITTED, HOWEVER LOCATION OF
 GENERATOR ETC WAS NOT SHOWN WITH THE NEW
 ELEVATION OF GEN ETC.
 "SLOSH" ELEVATION IS NOT REQUIRED ,
 HOWEVER 6" ABOVE BFE WILL BE REQUIRED.
  
 ** PREVIOUS NOTES **
 PLEASE KNOW, A SITE SURVEY AND
 ELEVATIONS WERE NOT SUBMITTED FOR
 LOCATION OF GENERATOR AND BFE.
 PLEASE SEE LOCATIONS OF GEN IN
 NFPA-110,7.2.3* WHICH REFERENCES THE
 "SLOSH" CHARTS.
  
 4)NOTE: NO, PLEASE SEE NO SPECS ETC WERE
 SUBMITTED AND ARE REQUIRED AT THIS TIME.
 PLEASE KNOW, IF THE EQUIPMENT HAS NOT
 BEEN PURCHASED, PICK ONE , IT ONLY NEEDS
 TOMEET ALL LISTINGS BY A NRTL, AND TO
 CORRELATE WITH ALL THE CODE REQUIREMENTS
 FOR INSTALLATION ETC. **THE EQUIPMENT
 CAN BE REVISED AT A LATER DATE IF
 DIFFERENT EQUIPMENT IS CHOSEN.
  
 **PREVIOUS NOTE **
 PLEASE SUBMIT ALL THE
 MANUFACTURE'S CUT/SPEC SHEETS FOR
 GENERATOR, ATS, AND ANY NEW FUEL
 TANK(S). PLEASE BE SURE ALL SPECS/SHEETS
 CONTAIN LISTINGS FROM A NRTL.
 215.5
  
 5)NOTE: NO, PLEASE SEE MOST HAS BEEN
 CLEARED UP, HOWEVER PLEASE SEE RISER AND
 NOTES ON E-1, AS NOTES #4 AND #7, SEEM
 TO BE CROSSED.??
 PLEASE SEE NO SIZES ARE PROVIDED FOR NEW
 MAIN, ATS ETC.
  
 ** PREVIOUS NOTE**
 PLEASE CORRELATE RISER ON E-1,
 WITH RISER ON E-2.
 PLEASE SEE NOTE #7 WHICH MENTIONS NEW
 CONDUITS FROM NEW MAIN, HOWEVER RISER
 SHOWS THIS AS EXIST TO REMAIN AND IS
 ALSO NOTED AS EXIST??
 PLEASE SEE NOTE #3, WHICH SHOWS THIS
 NOTE FOR WHAT APPEARS TO BE A METER
 BEING REMOVED AND MAIN DISCONNECT?
 (MISPRINT?)
 PLEASE SEE RISER, AS SHOWN SEEMS TO BE
 MISPRINTED BACKWARDS ,??
  
 6)NOTE: OK, HOWEVER PLEASE LIST
 EQUIPMENT WHICH IS LOCATED IN MAIN
 ELECTRICAL RM AS EXISTING WHERE
 APPLICABLE.
  
 7)NOTE: OK.
  
 8)NOTE: NO, PLEASE SEE VALUE WAS NOT
 ADJUSTED. PLEASE KNOW, A VALUE WILL BE
 PLACED ON THE SCOPE OF WORK BY SUING THE
 "MARSHALL'S/ SWIFT" GUIDE IF NOT
 INCREASED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 2004 FBC 108.3 CITY
 OF WEST PALM BEACH ADMINISTRATIVE CODE
 WHICH REQUIRES VALUE FOR SCOPE OF
 WORK/IMPROVEMENT TO INCLUDE ALL LABOR
 AND MATERIALS, EVEN IF EQUIPMENT IS
 OWNER SUPPLIED.
 PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF
 WORK.
  
 9)NOTE:NO, PLEASE SEE NO SLAB PLANS,
 DETAILS ETC WERE SUBMITTED AND ARE
 REQUIRED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS
 AS NO SLAB DETAIL WAS SUBMITTED. PLEASE
 SEE MIN REQUIREMENTS IN NFPA-110 AND
 ENGINEERING PRACTICES FOR A GENERATOR OF
 THIS SIZE AND WEIGHT.
 7.2.1.1,7.4, 7.5*
  
 ** NEW NOTE **
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  