2006-06-29 00:00:00 | ********** UNSAT 2ND REVIEW ************ |
| |
| ** PLEASE SEE THE FOLLOWING NOTES AS ALL |
| INFORMATION NEEDED WAS NOT SUBMITTED. |
| |
| ** PLEASE SEE SOME OF THE SAME NOTES |
| FROM PREVIOUS REVIEW STILL APPLY. |
| PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW. |
| |
| |
| 1)NOTE: OK |
| |
| 2)NOTE: OK. |
| |
| 3)NOTE: NO, PLEASE SEE AN OLD SITE PLAN |
| WAS SUBMITTED, HOWEVER LOCATION OF |
| GENERATOR ETC WAS NOT SHOWN WITH THE NEW |
| ELEVATION OF GEN ETC. |
| "SLOSH" ELEVATION IS NOT REQUIRED , |
| HOWEVER 6" ABOVE BFE WILL BE REQUIRED. |
| |
| ** PREVIOUS NOTES ** |
| PLEASE KNOW, A SITE SURVEY AND |
| ELEVATIONS WERE NOT SUBMITTED FOR |
| LOCATION OF GENERATOR AND BFE. |
| PLEASE SEE LOCATIONS OF GEN IN |
| NFPA-110,7.2.3* WHICH REFERENCES THE |
| "SLOSH" CHARTS. |
| |
| 4)NOTE: NO, PLEASE SEE NO SPECS ETC WERE |
| SUBMITTED AND ARE REQUIRED AT THIS TIME. |
| PLEASE KNOW, IF THE EQUIPMENT HAS NOT |
| BEEN PURCHASED, PICK ONE , IT ONLY NEEDS |
| TOMEET ALL LISTINGS BY A NRTL, AND TO |
| CORRELATE WITH ALL THE CODE REQUIREMENTS |
| FOR INSTALLATION ETC. **THE EQUIPMENT |
| CAN BE REVISED AT A LATER DATE IF |
| DIFFERENT EQUIPMENT IS CHOSEN. |
| |
| **PREVIOUS NOTE ** |
| PLEASE SUBMIT ALL THE |
| MANUFACTURE'S CUT/SPEC SHEETS FOR |
| GENERATOR, ATS, AND ANY NEW FUEL |
| TANK(S). PLEASE BE SURE ALL SPECS/SHEETS |
| CONTAIN LISTINGS FROM A NRTL. |
| 215.5 |
| |
| 5)NOTE: NO, PLEASE SEE MOST HAS BEEN |
| CLEARED UP, HOWEVER PLEASE SEE RISER AND |
| NOTES ON E-1, AS NOTES #4 AND #7, SEEM |
| TO BE CROSSED.?? |
| PLEASE SEE NO SIZES ARE PROVIDED FOR NEW |
| MAIN, ATS ETC. |
| |
| ** PREVIOUS NOTE** |
| PLEASE CORRELATE RISER ON E-1, |
| WITH RISER ON E-2. |
| PLEASE SEE NOTE #7 WHICH MENTIONS NEW |
| CONDUITS FROM NEW MAIN, HOWEVER RISER |
| SHOWS THIS AS EXIST TO REMAIN AND IS |
| ALSO NOTED AS EXIST?? |
| PLEASE SEE NOTE #3, WHICH SHOWS THIS |
| NOTE FOR WHAT APPEARS TO BE A METER |
| BEING REMOVED AND MAIN DISCONNECT? |
| (MISPRINT?) |
| PLEASE SEE RISER, AS SHOWN SEEMS TO BE |
| MISPRINTED BACKWARDS ,?? |
| |
| 6)NOTE: OK, HOWEVER PLEASE LIST |
| EQUIPMENT WHICH IS LOCATED IN MAIN |
| ELECTRICAL RM AS EXISTING WHERE |
| APPLICABLE. |
| |
| 7)NOTE: OK. |
| |
| 8)NOTE: NO, PLEASE SEE VALUE WAS NOT |
| ADJUSTED. PLEASE KNOW, A VALUE WILL BE |
| PLACED ON THE SCOPE OF WORK BY SUING THE |
| "MARSHALL'S/ SWIFT" GUIDE IF NOT |
| INCREASED. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE 2004 FBC 108.3 CITY |
| OF WEST PALM BEACH ADMINISTRATIVE CODE |
| WHICH REQUIRES VALUE FOR SCOPE OF |
| WORK/IMPROVEMENT TO INCLUDE ALL LABOR |
| AND MATERIALS, EVEN IF EQUIPMENT IS |
| OWNER SUPPLIED. |
| PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF |
| WORK. |
| |
| 9)NOTE:NO, PLEASE SEE NO SLAB PLANS, |
| DETAILS ETC WERE SUBMITTED AND ARE |
| REQUIRED. |
| |
| ** PREVIOUS NOTE** |
| PLEASE SEE BLDG REVIEW COMMENTS |
| AS NO SLAB DETAIL WAS SUBMITTED. PLEASE |
| SEE MIN REQUIREMENTS IN NFPA-110 AND |
| ENGINEERING PRACTICES FOR A GENERATOR OF |
| THIS SIZE AND WEIGHT. |
| 7.2.1.1,7.4, 7.5* |
| |
| ** NEW NOTE ** |
| |
| 10) NOTE: PLEASE SEE FS 553.80(2)(B) |
| WITH RESPECT TO REPEAT COMMENTS. |
| |
| |
| ** PLEASE SEE POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |