Plan Review Notes
Plan Review Notes For Permit 06011059
Permit Number 06011059
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-28 00:00:00*********** UNSAT ************
  
 ** PLEASE SEE THE FOLLOWING NOTES AS ALL
 INFORMATION NEEDED WAS NOT SUBMITTED.
  
  
 1)NOTE: PLEASE KNOW, THE ADDRESS AND
 SITE BE ON TITLE BLOCK OF PLANS. PLEASE
 KNOW, THE ADDRESS IS 951 OKEECHOBEE RD,
 AND NOT "OLD" OKEECHOBEE AS ON PERMIT
 APPLICATION.
  
 2)NOTE: PLEASE REFERENCE ALL CURRENTS
 CODES FOR INSTALLATION OF THIS PROJECT.
 PLEASE SEE 2003 NFPA-101, 2002 NFPA-110,
 NFPA-70 2002.
  
 3)NOTE: PLEASE KNOW, A SITE SURVEY AND
 ELEVATIONS WERE NOT SUBMITTED FOR
 LOCATION OF GENERATOR AND BFE.
 PLEASE SEE LOCATIONS OF GEN IN
 NFPA-110,7.2.3* WHICH REFERENCES THE
 "SLOSH" CHARTS.
  
 4)NOTE: PLEASE SUBMIT ALL THE
 MANUFACTURE'S CUT/SPEC SHEETS FOR
 GENERATOR, ATS, AND ANY NEW FUEL
 TANK(S). PLEASE BE SURE ALL SPECS/SHEETS
 CONTAIN LISTINGS FROM A NRTL.
 215.5
  
 5)NOTE: PLEASE CORRELATE RISER ON E-1,
 WITH RISER ON E-2.
 PLEASE SEE NOTE #7 WHICH MENTIONS NEW
 CONDUITS FROM NEW MAIN, HOWEVER RISER
 SHOWS THIS AS EXIST TO REMAIN AND IS
 ALSO NOTED AS EXIST??
 PLEASE SEE NOTE #3, WHICH SHOWS THIS
 NOTE FOR WHAT APPEARS TO BE A METER
 BEING REMOVED AND MAIN DISCONNECT?
 (MISPRINT?)
 PLEASE SEE RISER, AS SHOWN SEEMS TO BE
 MISPRINTED BACKWARDS ,??
  
 6)NOTE: PLEASE SEE EXISTING RISER SHOWS
 A EXISTING GEN DISC LCOATED INSIDE,
 NOTED TO BE REMOVED, YET NEW REVISED
 RISER SHOWS THIS DISCONNECT STILL
 LOCATED ON REVISED RISER? PLEASE
 CLARIFY, IF THE GEN DISC LOCATED INSIDE
 BLDG, IS BEING REMOVED. ALL ELECTRICAL
 EQUIPMENT NO LONGER IN USE SHOULD BE
 REMOVED.
  
 7)NOTE: PLEASE PROVIDE OCP AT GENERATOR,
 PLEASE ALSO SEE 445.13.
 UNABLE TO VERIFY FEEDER SIZES, ETC .
 215.5
  
  
 8)NOTE: PLEASE SEE 2004 FBC 108.3 CITY
 OF WEST PALM BEACH ADMINISTRATIVE CODE
 WHICH REQUIRES VALUE FOR SCOPE OF
 WORK/IMPROVEMENT TO INCLUDE ALL LABOR
 AND MATERIALS, EVEN IF EQUIPMENT IS
 OWNER SUPPLIED.
 PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF
 WORK.
  
 9)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS NO SLAB DETAIL WAS SUBMITTED. PLEASE
 SEE MIN REQUIREMENTS IN NFPA-110 AND
 ENGINEERING PRACTICES FOR A GENERATOR OF
 THIS SIZE AND WEIGHT.
 7.2.1.1,7.4, 7.5*
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]