Plan Review Notes For Permit 06011029 |
Permit Number |
06011029 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-30 00:00:00 | | | PROVISO | | ~~~~~~~ | | | | 1} THE KITCHEN DETAIL IS NOT CLEAR | | ENOUGH TO VERIFY COMPLIANCE WITH | | 210.52(C). RESUBMIT WITH KITCHEN DETAIL | | OR MORE CLARITY ON THE FLOOR PLAN, | | PERHAPS A LARGER SCALE DRAWING. | | | | 2} INDICATE THE NEW PANEL LOCATION | | REFERRED TO IN THE NOTES. | | | | 3} PLEASE PROVIDE A PANEL SCHEDULE SO | | THAT BRANH CIRCUIT COMPLIANCE CAN BE | | REVIEWED. | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | PRIOR TO CALLING A ROUGH INSPECTION, | | ALLOW AT LEAST ONE WEEK FOR THE REVIEW | | PROCESS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|