2006-05-16 00:00:00REVISION: INDICATE FIRE VALVE ON
 ISOMETRIC
  
  
 ******PROVISO******
 PER NFPA-96 SEC. 10.5.1, AND NFPA-1 SEC.
 50.4.7.1: A READILY ACCESSIBLE MEANS FOR
 MANUAL ACTIVATION SHALL BE LOCATED
 BETWEEN 42 INCH AND 48 INCH ABOVE THE
 FLOOR, BE ACCESSIBLE IN THE EVENT OF A
 FIRE, BE LOCATED IN A PATH OF EGRESS,
 AND CLEARLY IDENTIFY THE HAZARD
 PROTECTED.