Plan Review Notes For Permit 06011008 |
Permit Number |
06011008 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-16 00:00:00 | REVISION: INDICATE FIRE VALVE ON | | ISOMETRIC | | | | | | ******PROVISO****** | | PER NFPA-96 SEC. 10.5.1, AND NFPA-1 SEC. | | 50.4.7.1: A READILY ACCESSIBLE MEANS FOR | | MANUAL ACTIVATION SHALL BE LOCATED | | BETWEEN 42 INCH AND 48 INCH ABOVE THE | | FLOOR, BE ACCESSIBLE IN THE EVENT OF A | | FIRE, BE LOCATED IN A PATH OF EGRESS, | | AND CLEARLY IDENTIFY THE HAZARD | | PROTECTED. |
|