2006-01-30 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. IF THE TANK IS BELOW GROUND THE
 CONTAINER SHALL BE SECURLY ANCHORED PER
 NFPA 58.(DETAIL REQUIRED)
 2. INDICATE ON ISOMETRIC DRAWINGS SHUT
 OFF VALVES, AND REGULATORS ALSO INDICATE
 THE MAKE AND MODEL NUMBER OF REGULATORS.
 (ADD TO DRAWINGS)
 3. NOTE AS OF OCT. 1ST 2004 FBC-2004
 FUEL GAS CODES IN EFFECT, PLEASE SEE IC-
 CLOSED U/G PE TABLE FROM NFPA 58 AND USE
 FOR FUTURE REFERENCE BECAUSE SUCH TABLE
 NOT GIVEN IN FBC-2004 FUEL GAS CODE BOOK
  
 END OF COMMENTS:
  