Plan Review Notes For Permit 06010882 |
Permit Number |
06010882 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-30 00:00:00 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PERMIT: | | | | 1. IF THE TANK IS BELOW GROUND THE | | CONTAINER SHALL BE SECURLY ANCHORED PER | | NFPA 58.(DETAIL REQUIRED) | | 2. INDICATE ON ISOMETRIC DRAWINGS SHUT | | OFF VALVES, AND REGULATORS ALSO INDICATE | | THE MAKE AND MODEL NUMBER OF REGULATORS. | | (ADD TO DRAWINGS) | | 3. NOTE AS OF OCT. 1ST 2004 FBC-2004 | | FUEL GAS CODES IN EFFECT, PLEASE SEE IC- | | CLOSED U/G PE TABLE FROM NFPA 58 AND USE | | FOR FUTURE REFERENCE BECAUSE SUCH TABLE | | NOT GIVEN IN FBC-2004 FUEL GAS CODE BOOK | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 |
|