Date |
Text |
2006-03-24 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| CITY CODE WPB |
| |
| 1. MINIMUM FACILITIES PER TABLES |
| 1004.1.2 AND 104.3 REQUIRE 5 WATER |
| CLOSETS, AND 4 LAVS. ONLY ONE WATER |
| CLOSET AND ONE LAV IS SHOWN. |
| 2. SUBMIT A DETAIL FOR THE ACCESSIBLE |
| TOILET ROOMS. SHOW THE FOLLOWING: |
| FOR THE W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.4 GRAB BARS |
| D. 11-4.16.5 FLUSH CONTROLS |
| E. 11-4.16.6 DISPENSERS |
| FOR THE LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| E. 11-4.19.6 MIRRORS |
| FOR THE TOILET ROOMS: |
| A. 11-4.22.3 5' TURNING AREA |
| 3. SUBMIT A DETAIL FOR THE DRINKING |
| FOUNTAIN REQUIRED TO BE ACCESSIBLE PER |
| SECTION 11-4.1.3(10). DRINKING FOUNTAINS |
| APPEAR TO BE HI/LOW, IF NOT SHOW |
| COMPLIANCE WITH SECTION 11-4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| BENDING OR STOOPING. |
| 4. SHT A-5 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. |
| SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS. SHOW THE SQUARE FOOTAGE |
| AREA BEING DRAINED FOR EACH DRAIN ALONG |
| WITH 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS BEING ADDED TO THE |
| AREA OF THE ROOF. |
| 5. SCUPPER DRAINS SHALL BE SIZED IN |
| ACCORDANCE WITH TABLE 1106.7, & SECTIONS |
| 1107.3 AND 1101.7. THE SIZING OF THE |
| SCUPPERS CAN NOT BE DETERMINED WITHOUT |
| REFERENCE TO THE DEFLECTION OF THE ROOF. |
| PLEASE STATE ON THE PLANS THAT SCUPPER |
| SIZES COMPLY WITH SECTIONS AND TABLE |
| MENTIONED ABOVE. |
| 6. AHT A-8.2 BUILDING SECTION INDICATES |
| THE SCUPPER TO BE 8" ABOVE THE ROOF. PER |
| SECTION 1503.4.3, OVERFLOW SCUPPERS |
| SHALL BE PLACED IN WALLS NOT LESS THEN |
| 2" OR MORE THAN 4" ABOVE THE FINISHED |
| ROOF COVERING. |
| 7. SHT MP-1 DRAINAGE LINES INDICATE 4" |
| RD, 2" CONDENSATE & 4" SANITARY ALL |
| COMBINED IN ONE DRAINAGE LINE. THIS IS |
| NOT APPROVED PER SECTIONS 125-90(5) AND |
| 90-203 OF THE CITY OF WEST PALM BEACH |
| MUNICIPAL CODE. SEPARATE SANITARY, STORM |
| AND CONDENSATE LINE ARE REQUIRED. SHOW |
| THE PIPING FOR THESE SYSTEMS ON THE FLAT |
| DRAWINGS TO REFLECT THE REQUIRED RISER |
| DIAGRAMS. CONDENSATE SHALL DRAIN |
| SEPARATELY OUT OF THE BUILDING, BUT CAN |
| TIE INTO THE STORM LINES OUTSIDE THE |
| BUILDING AND SHALL HAVE A RELIEF VENT, |
| (GOOSE NECK), INSTALLED AS THE |
| CONDENSATE EXITS THE BUILDING. |
| 8. SUBMIT A SANITARY RISER ISOMETRIC |
| DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, |
| VENTS ETC. THE RISER DIAGRAM SHALL SHOW |
| ALL PIPING FROM 5' OUTSIDE THE BUILDING, |
| ALL BUILDING DRAIN PIPING, ALL FIXTURE |
| PIPING, INCLUDING FUTURE STUBOUTS FOR |
| DRAINAGE AND VENT, AND INDICATE DRAINAGE |
| FIXTURE UNITS AS THEY ACCUMULATE IN THE |
| SYSTEM. SECTION 106.3.5.1.3(4). |
| 9. SUBMIT A STORM ISOMETRIC RISER |
| DIAGRAM. SHOW ALL PIPE SIZES, VERTICAL |
| RISERS, AND INDICATE THE SQUARE FOOTAGE |
| AS IT ACCUMULATES IN THE SYSTEM. SECTION |
| 106.3.5.1.3(7). |
| 10. SUBMIT A WATER ISOMETRIC RISER |
| DIAGRAM SHOW ALL PIPE SIZES, VALVES, AND |
| WATER HAMMER ARRESTORS IF REQUIRED BY |
| SECTION 604.9. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING. |
| RISER DIAGRAM SHALL SHOW ALL PIPING FROM |
| THE ENTRANCE TO THE BUILDING TO THE LAST |
| FIXTURE INCLUDING ALL FUTURE STUBOUTS |
| WITH VALVES AND CAPS. SECTION |
| 106.3.5.1.3(10). |
| 11. PLANS SEEM INCOMPLETE AND MORE |
| COMMENTS MAY BE FORTHCOMING DEPENDING ON |
| THE COMMENT RESPONSES AND ADDED |
| INFORMATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |