2006-03-13 00:00:00 | DENIED: |
| 1.PLAN INDICATES A BASEMENT LEVEL. |
| PLEASE PROVIDE OUTSIDE AIR CALCULATIONS |
| IN ACCORDANCE WITH 2004 FMC 404.1 |
| THROUGH 404.3. |
| |
| 2.PLAN SHEET MP-1 INDICATES AC-1, |
| PLEASE PROVIDE HANGING DETAIL. |
| |
| 3.PLAN SHEET M-1 PLEASE PROVIDE |
| INFORMATION ON VENTILATION TO THE |
| STORAGE AREAS. |
| |
| 4.PLAN SHEET MP-2 PLEASE CLARIFY THE |
| RATING OF THE WALL WHERE EF-2 |
| TERMINATES.PROVIDE DISTANCE TO THE |
| PROPERTY LINE. SHOW COMPLIANCE WITH 2004 |
| FMC 401.5, 401.5.2, & 501.2. |
| |
| 5.PLEASE CLARIFY THE MECHANICAL CHASE |
| WITH EXHAUST, FRESH AIR DUCT, & PIPING. |
| SHOW COMPLIANCE WITH NFPA 90A-02 |
| 5.3.4.5.PLEASE NOTE, ACCESS FOR |
| SERVICE & INSPECTION OF THE HORIZONTAL |
| FIRE DAMPER. |
| |
| 6.PLEASE CLARIFY THE RATING OF THE |
| CEILING/ROOF ASSEMBLY. |
| |
| 7.PLEASE PROVIDE DETAIL FOR THE ROOF |
| JACK, GOOSENECK & THE CONDENSING UNIT |
| STANDS.STANDS AND CURBS SHALL COMPLY |
| WITH 2004 FBC 1509.7. |
| |
| PLANS APPEAR TO BE FOR A "SHELL |
| BUILDING" ONLY.ADDITIONAL EQUIPMENT |
| AND DUCT LAYOUT WILL BE REQUIRED FOR THE |
| INTERIOR BUILD-OUT. |
| |