Plan Review Notes
Plan Review Notes For Permit 06010854
Permit Number 06010854
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-13 00:00:00DENIED:
 1.PLAN INDICATES A BASEMENT LEVEL.
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 IN ACCORDANCE WITH 2004 FMC 404.1
 THROUGH 404.3.
  
 2.PLAN SHEET MP-1 INDICATES AC-1,
 PLEASE PROVIDE HANGING DETAIL.
  
 3.PLAN SHEET M-1 PLEASE PROVIDE
 INFORMATION ON VENTILATION TO THE
 STORAGE AREAS.
  
 4.PLAN SHEET MP-2 PLEASE CLARIFY THE
 RATING OF THE WALL WHERE EF-2
 TERMINATES.PROVIDE DISTANCE TO THE
 PROPERTY LINE. SHOW COMPLIANCE WITH 2004
 FMC 401.5, 401.5.2, & 501.2.
  
 5.PLEASE CLARIFY THE MECHANICAL CHASE
 WITH EXHAUST, FRESH AIR DUCT, & PIPING.
 SHOW COMPLIANCE WITH NFPA 90A-02
 5.3.4.5.PLEASE NOTE, ACCESS FOR
 SERVICE & INSPECTION OF THE HORIZONTAL
 FIRE DAMPER.
  
 6.PLEASE CLARIFY THE RATING OF THE
 CEILING/ROOF ASSEMBLY.
  
 7.PLEASE PROVIDE DETAIL FOR THE ROOF
 JACK, GOOSENECK & THE CONDENSING UNIT
 STANDS.STANDS AND CURBS SHALL COMPLY
 WITH 2004 FBC 1509.7.
  
 PLANS APPEAR TO BE FOR A "SHELL
 BUILDING" ONLY.ADDITIONAL EQUIPMENT
 AND DUCT LAYOUT WILL BE REQUIRED FOR THE
 INTERIOR BUILD-OUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.