Plan Review Notes
Plan Review Notes For Permit 06010854
Permit Number 06010854
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5. BUILDING WILL BE REQUIRED TO BE FIRE
 SPRINKLERED IN ACCORDANCE WITH 553.895
 (2).
  
 6. THE ELECTRICAL DRAWINGS NEED TO BE
 EXAMINED. IT DOES NOT APPEAR ENOUGH EXIT
 SIGNS OR EMERGENCY LIGHTS EXIST OR ARE
 CALLED OUT ON THE DRAWINGS. EXIT SIGNS
 SHALL NOT EXCEED 100 FEET APART. ALL
 EXITS SHALL BE CLEARLY IDENTIFIED AND
 MARKED.
  
 7. PLEASE EXPLAIN 6" RISERS FOR
 MONUMENTAL STAIR.
  
 8. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINUMUM OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED.
  
 9. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 10. PLEASE PROVIDE MORE DETAILS ON
 EXHAUST FAN 2. WHEN DOES IT RUN AND WHAT
 OCCURS WHEN LOSS OF POWER OCCURS TO THE
 BUILDING.
  
 11. NO EXIT SIGNS SHOWN ON PAGE E-2,
 GROUND LEVEL.
  
 12. ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 13. PLEASE PROVIDE A LIFE SAFETY PLAN
 ILLUSTRATING EXIT ROUTES, TRAVEL
 DISTANCES, ANY DEAD-END CONDITIONS, ETC.
  
 14. COULD NOT LOCATE ANY EXISTING OR NEW
 FIRE HYDRANTS ON WATER AND SANITARY
 SEWER PLANS.
  
 15. NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 16. THIS OFFICE WILL NOT ACCEPT THE FIRE
 ALARM CONTROL PANEL IN THE BASEMENT.
 PLEASE REVISE DRAWING.
  
 17. DOOR SCHEDULE DOES NOT ILLUSTRATE
 REQUIRED FIRE RATINGS. PLEASE REVISE
 PLANS.
  
 18. A MINIMUM OF AT LEAST A TWO HOUR
 HORIZONTAL FIRE SEPERATION IS REQUIRED
 BETWEEN THE PARKING AREA AND OTHER
 PORTIONS OF THE BUILDING.
  
 19. PLEASE DISPLAY FIRE EXTINGUISHER
 LOCATIONS.
  
 20. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR ALL WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION