2006-02-16 00:00:00 | 1. DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH NFPA 241. |
| |
| 2. EXIT STAIRS ARE TO BE KEPT UP WITH |
| CONSTRUCTION. |
| |
| 3. DEBRIS SHALL BE REMOVED FROM THE SITE |
| DAILY. |
| |
| 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 5. BUILDING WILL BE REQUIRED TO BE FIRE |
| SPRINKLERED IN ACCORDANCE WITH 553.895 |
| (2). |
| |
| 6. THE ELECTRICAL DRAWINGS NEED TO BE |
| EXAMINED. IT DOES NOT APPEAR ENOUGH EXIT |
| SIGNS OR EMERGENCY LIGHTS EXIST OR ARE |
| CALLED OUT ON THE DRAWINGS. EXIT SIGNS |
| SHALL NOT EXCEED 100 FEET APART. ALL |
| EXITS SHALL BE CLEARLY IDENTIFIED AND |
| MARKED. |
| |
| 7. PLEASE EXPLAIN 6" RISERS FOR |
| MONUMENTAL STAIR. |
| |
| 8. BUILDING ADDRESS REQUIRED ON PROPER |
| ELEVATION. A MINUMUM OF AT LEAST 6" HIGH |
| NUMBERS ARE REQUIRED. |
| |
| 9. SEPERATE PLANS AND PERMITS REQUIRED |
| FOR FIRE ALARM SYSTEM. THE FIRE ALARM |
| SYSTEM SHALL BE MONITORED BY A LICENSED |
| UL LISTED CENTRAL STATION APPROVED FOR |
| CENTRAL STATION SERVICE. |
| |
| 10. PLEASE PROVIDE MORE DETAILS ON |
| EXHAUST FAN 2. WHEN DOES IT RUN AND WHAT |
| OCCURS WHEN LOSS OF POWER OCCURS TO THE |
| BUILDING. |
| |
| 11. NO EXIT SIGNS SHOWN ON PAGE E-2, |
| GROUND LEVEL. |
| |
| 12. ELECTRONIC SWITCHES, CHAIN AND LOCK |
| REQUIRED ON FIRE LINE BACKFLOW DEVICE. |
| |
| 13. PLEASE PROVIDE A LIFE SAFETY PLAN |
| ILLUSTRATING EXIT ROUTES, TRAVEL |
| DISTANCES, ANY DEAD-END CONDITIONS, ETC. |
| |
| 14. COULD NOT LOCATE ANY EXISTING OR NEW |
| FIRE HYDRANTS ON WATER AND SANITARY |
| SEWER PLANS. |
| |
| 15. NO FIRE SPRINKLER DRAWINGS PROVIDED |
| WITH PLANS. |
| |
| 16. THIS OFFICE WILL NOT ACCEPT THE FIRE |
| ALARM CONTROL PANEL IN THE BASEMENT. |
| PLEASE REVISE DRAWING. |
| |
| 17. DOOR SCHEDULE DOES NOT ILLUSTRATE |
| REQUIRED FIRE RATINGS. PLEASE REVISE |
| PLANS. |
| |
| 18. A MINIMUM OF AT LEAST A TWO HOUR |
| HORIZONTAL FIRE SEPERATION IS REQUIRED |
| BETWEEN THE PARKING AREA AND OTHER |
| PORTIONS OF THE BUILDING. |
| |
| 19. PLEASE DISPLAY FIRE EXTINGUISHER |
| LOCATIONS. |
| |
| 20. PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR ALL WALLS AND |
| CEILINGS. |
| |
| MIKE CARSILLO, CHIEF FIRE PREVENTION |
| OFFICER |
| 804-4709 |