Plan Review Notes
Plan Review Notes For Permit 06010854
Permit Number 06010854
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-27 00:00:00*********UNSAT *********
  
 1)NOTE: PLEASE SEE TITLE BLOCK ON PLANS
 SHALL INDICATE THE ADDRESS AND LOCATION
 OF PROJECT.
 FAC 61G15-23.002,61G1-16.003
  
 2)NOTE: PLEASE BE SURE THE FOLLOWING
 CODES IN EFFECT ARE REFERENCED:
 2003 NFPA-101, 2002 NFPA-72, 2002
 NFPA-70.
 PLEASE SEE SOME CODES ETC ARE REFERENCED
 FROM THE 2001 FBC.
  
 3)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS NEW MEDICAL OFFICE BLDG,
 HOWEVER NO INTERIOR PLANS WERE
 SUBMITTED. PLEASE SEE NOT EM/ EXT LTS
 PER FIRE REVIEW COMMENTS?
  
 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR TOWERS AS NEW STAIRS IN 2003
 LS101, 7.8.1.3 REQUIRES 10FT CANDLES,
 UNDER NORMAL POWER AND 1FT CANDLE MIN
 UNDER EM. 7.9.2.2
 PLEASE ALSO SEE EM LTS FOR EGRESS PATH
 IN PARKING GARAGE COOULD NOT BE LOCATED.
 PLEASE ALSO PROVIDE A BATTERY BACK UP LT
 FIXTURE OF SOME SORT IN MAIN ELECTRICAL
 RM, ELEVATOR MACHINE RM AND LOCATION
 WHERE FACP IS BEING MOVED TO PER FIRE
 REVIEW COMMENTS.
 7.8,7.9,700.16, 700.12E ETC.
  
 5)NOTE: PLEASE SEE FBC 2004 CHAPTER 13,
 FOR COMMERCIAL BLDGS. PLEASE SEE
 13-413.1.ABC.1.1 &.2 FOR VOLTAGE DROP
 INFORMATIO TO BE PROVIDED.
 PLEASE SEE VERIFY COMPLIANCE FOR
 INTERIOR OF BLDG IF IN SCOPE OF WORK?
  
 6)NOTE: PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR POWER FOR FAN POWER IN THE
 EVENT OF POWERE FAILURE, GATE CONTROLS
 FOR OPERATION OF THESE GATES AFTER POWER
 HAS BEEN LOST.
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER TRADES WHICH WILL AFFETC
 ELECTRICAL PLANS.
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  