Date |
Text |
2006-03-14 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL ARCHITECTURAL SHEETS. A DATED |
| SEAL IS REQUIRED, AND THE ARCHITECTS |
| TITLE BLOCK SHALL BE UPDATED WITH THE |
| CORRECT ADDRESS. (SEE ATTACHED SHEET |
| FROM FLORIDA DBPR). FAC |
| 61G1-16.004(1)(5) AND FS 481.2055. |
| 2. SHT A1 SHOWS A FOUNTAIN. THIS IS NOT |
| INDICATED ON THE APPLICATION "DESCRIBE |
| PROJECT IN DETAIL". WILL THIS BE ON A |
| SEPARATE PERMIT WITH SEPARATE PLANS? THE |
| VALUE OF THE FOUNTAIN SHALL BE WITH THE |
| SEPARATE PLANS/PERMIT. |
| 3. SHT A2 FOUNTAIN PUMP. SUBMIT MANUF. |
| SPECIFICATIONS FOR FOUNTAIN PUMP. PUMP |
| SHALL BE LISTED. SECTION 303.4 |
| 4. SHT A2 PER TABLE 403.1 A DRINKING |
| FOUNTAIN IS REQUIRED. SHOW THE LOCATION |
| ON THE FLOOR PLAN, AND SHOW PIPING ON |
| PLUMBING PLANS. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS, AND IF NOT A HI/LOW SHOW A |
| DETAIL FOR SECTION 11-4.15..1.3(10)(A) |
| REQUIREMENTS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| 5. SHT A2 ENTRY PLAZA INDICATES SLOPE TO |
| DRAIN. DRAIN NOT SHOWN. PLEASE CLARIFY. |
| SECTION 106.1.1. INDICATE WHAT AND WHERE |
| THE DRAIN WILL CONNECT TO. SUBMIT PIPING |
| PLANS SHOWING ALL PIPE SIZES ETC. |
| 106.3.5.1.3. |
| 6. SHT A5 TOILET ROOM ELEVATIONS. SHOW |
| THE FOLLOWING: |
| FOR W/C'S: |
| A. 11-4.16.5 FLUSH CONTROLS |
| FOR LAVS: |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| 7. SHT A8 DETAIL "A" SINK SHALL BE |
| ACCESSIBLE. DETAIL SHALL SHOW COMPLIANCE |
| WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. FORWARD APPROACH TO SINK |
| REQUIRED. A 5' TURNING AREA IS REQUIRED |
| IN SINK AREA. SECTION 11-4.2.3. |
| 8. ALL PLUMBING, MECHANICAL, & |
| ELECTRICAL SHEETS, ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME AND LICENSE |
| NUMBER AS WELL AS, THE NAME, ADDRESS, |
| AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS ON EACH |
| SHEET. FAC 61G15-23.002(2) & FS 471.025. |
| 9. SHT P2 SANT. RISER DIAGRAM, 3" IS |
| REQUIRED UP TO THE WASH MACHINE TEE. |
| SECTION 406.3. CLEANOUT SHALL BE MINIMUM |
| 4' ABOVE THE FLOOR FOR ACCESS. SECTION |
| 708.9. |
| 10. SHT P2 SANT. RISER DIAGRAM, HAIR |
| WASH SINKS, (GROUP OF 4), ARE NOT |
| VENTED. EITHER ISLAND VENTS OR AAV'S ARE |
| REQUIRED. SECTION 901.2.1. |
| 11. SHT P2 WATER RISER DIAGRAM, WATER |
| HAMMER ARRESTORS ARE REQUIRED AT THE |
| WASH MACHINE AND AT THE REF. ICE MAKER. |
| SECTION 604.9. THESE SHALL BE LOCATED |
| NEAR THE FIXTURES IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. |
| PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. |
| 12. SHT P2 PLUMBING SPECIFICATIONS #13 |
| INDICATES "K COPPER" FOR UNDERGROUND. |
| RISERS DIAGRAM SHOWS FITTINGS. NO SOLDER |
| JOINTS ARE APPROVED UNDER THE SLAB. |
| PIPING SHOULD BE LOOPED FROM SINK TO |
| SINK WITH THE MANIFOLD ABOVE THE SLAB. |
| SECTION 604.10.3. |
| 13. AN RPZV BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE. SECTION 608.13.2. |
| BACKFLOW SHALL BE LOCATED AS CLOSE TO |
| THE WATER METER AS POSSIBLE ON PRIVATE |
| PROPERTY. |
| 14. SHT P2 PLUMBING NOTES #1 INDICATES |
| 120 GALLON WATER HEATER, BUT SHT A2 |
| FLOOR PLAN SHOWS AN 80 GALLON WATER |
| HEATER. PLEASE CORRELATE ARCHITECTURAL |
| AND PLUMBING SHEETS. SECTION 106.1.1. |
| 15. MORE INFORMATION IS REQUIRED ON THE |
| CONDENSATE SYSTEM. INDICATE HOW AHU'S |
| ARE TO BE DRAINED. SUBMIT A CONDENSATE |
| ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE |
| SIZES, AND TERMINATION POINT. INDICATE |
| MATERIAL TYPE. SECTION 106.3.5.1.3. |
| 16. SEPARATE PLANS REQUIRED FOR |
| FOUNTAIN. SHOW ALL PIPE SIZES AND ALL |
| PIPING FROM AND TO THE PUMP. INDICATE IF |
| THERE IS A DRAIN FOR THE FOUNTAIN AND |
| WHERE IT DRAINS TO. INDICATE IF THERE IS |
| A FILTER FOR THE SYSTEM, AND IF THERE IS |
| A WATER SUPPLY FOR THE FOUNTAIN. IF |
| THERE IS A WATER SUPPLY, BACKFLOW |
| PREVENTION IS REQUIRED. INDICATE METHOD |
| OF BACKFLOW PREVENTION. SECTIONS |
| 106.1.1. AND 608. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |