Plan Review Notes
Plan Review Notes For Permit 06010844
Permit Number 06010844
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-16 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 WHICH
 REQUIRED THE RAISED SEAL TO CHANGE FROM
 THE WORDING OF "CERTIFICATE" TO
 "LICENSE" BY 2/5/04, HOWEVER AN
 EXTENSION WAS GRANTED BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS TO
 DECEMBER 31,2005.
 PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE
 WORDING ON RAISED SEAL AS REQUIRED.
 FS 471.025
 ANY STAMPED PLANS SHALL BECOME "VOID".
  
  
 2)NOTE: PLEASE SUBMIT ELECTRICAL WIRING
 DIAGRAM/DETAIL FOR ALL FOUNTAIN
 EQUIPMENT AND WIRING.
 PLEASE PROVIDE GROUNDING DETAIL PER 680.
 PLEASE SHOW HOW EQUIPMENTON PLANS
  
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE SEE 700.12E WHICH REQUIRES THE
 EXT/ EM LTS TO BE CIRCUITED TO THE LOCAL
 LIGHTING IN ANY ONE AREA.
  
 4)NOTE: PLEASE CORRELATE PLANS WITH
 RISER, AS LIGHTING PLANS SHOW A PANEL
 LOCATED OUTSIDE , WHERE-AS POWER PLANS
 SHOWS AND NEW MAIN DISCONNECT AS RISER
 SHOWS.
  
 5)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER
 250.66. PLEASE SEE A 1/0 MIN IS
 REQUIRED.
 PLEASE ALSO SEE MISSING CWP AS REQUIRED
 PER 250.50,250.52A
  
 6)NOTE: PLEASE INCLUDE SEC'S FROM METER
 TO MAINS.
 215.5,240.4,310.16
  
 7)NOTE: PLEASE REFERENCE THE FOLLOWING
 CODES ON PLANS.
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 PLEASE ALSO SEE BLDG REVIEW COMMENTS AS
 REFERENCE TO THE 2004 FBC COULD NOT BE
 LCOATED.
  
 8)NOTE: PLEASE SEE POSSIBLE MISSING
 CA/FIRM LICENSE # FOR ARCHITECTUAL FIRM.
 61G1-16.004, FS 481.219
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASW KNOW, ALL OLD/VOIDED SHEETS
 MUST BE REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  