2006-02-09 00:00:00 | 1) 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. NOTE: THE NOTICE OF COMMENCEMENT |
| MUST BE RE-RECORDED IF THE DESCRIBED |
| IMPROVEMENT OR CONSTRUCTION IS NOT |
| COMMENCED WITHIN 90 DAYS OF RECORDING. |
| |
| 2) THERE IS NO GARAGE DOOR ON THIS |
| STRUCTURE SO,WHY IS IT CALL A |
| GARAGE/STUDIO? IF THE STRUCTURE WILL NOT |
| BE USED AS A GARAGE, CHANGE THE |
| DESCRIPTION ON THE APPLICATION TO MATCH |
| THE USE AND OCCUPANCY OF THE BUILDING. |
| |
| 3) PRODUCT APPROVALS WITH THE STATE |
| COVER SHEET AND FL# ARE NEEDED FOR EACH |
| PRODUCT INCLUDING THE ROOFING |
| MATERIALS/DOORS AND WINDOWS/LINTELS ETC. |
| THOSE PRODUCTS WHICH ARE GEGULATED BY |
| DCA RULE 9B72 SHALL BE REVIEW AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| (W.P.B.AMENDMENTS) 106.3.3 |
| |
| 4) THE LUS28 SIMPSON HANGER IS TOO SHORT |
| TO ACCOMIDATE A 2X12. I SUGGEST THAT YOU |
| SPEAK WITH SIMPSON STRONG TIE AND GET |
| THEIR ADVISE AS TO WHICH HANGE SHOULD BE |
| USED. |
| |
| 5) 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL |
| BE DIMENSIONED AND DRAWN UPON SUITABLE |
| MATERIAL. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE |
| BUILDING OFFICIAL (SEE ALSO SECTION |
| 106.3.5). |
| |
| 6) 106.1.1.2 FOR ROOF ASSEMBLIES |
| REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL ILLUSTRATE, DESCRIBE, |
| AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND |
| WIND RESISTANCE RATING THAT ARE REQUIRED |
| TO BE INSTALLED.PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE |
| WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE OR A STATEMENT BY AN |
| ARCHITECT OR ENGINEER FOR THE SPECIFIC |
| SITE MUST BE SUBMITTED WITH THE |
| CONSTRUCTION DOCUMENTS.ALSO SEE ROOFING |
| PROCEDURE IN PACKAGE. |
| |
| 7) NOTE: THE WIND LOAD SECTION IN THE |
| FBC IS 1609 NOT 1606. CHANGE NOTES TO |
| REFLECT THE CORRECT SECTION. |
| |
| 8)A SITE PLAN IS REQUIRED SHOWING THE |
| EXACT OUTLINE,SIZE AND LOCATION OF |
| PROPOSED ADDITION AND EXISTING BUILDINGS |
| AND SHOW DISTANCE TO PROPERTY LINES.ETC. |
| SITE DRAWINGS. DRAWINGS SHALL SHOW THE |
| LOCATION OF ALL NEW WORK, INCLUDING THE |
| PROPOSED BUILDING OR STRUCTURE, AND OF |
| ALL EXISTING MAN-MADE IMPROVEMENTS AND |
| EVERY EXISTING SURVEY, OR OTHER SPECIAL |
| SURVEY, PREPARED BY A QUALIFIED |
| SURVEYOR. IF REQUIRED, SURVEYS SHALL BE |
| PREPARED IN ACCORDANCE WITH PROVISIONS |
| OF CHAPTERS 177 AND 472 FLORIDA |
| STATUTES, AND RULE 61G17, FLORIDA |
| ADMINISTRATIVE CODE. (W.P.B AMENDMENTS |
| SEC.106.3.4) |
| |