Plan Review Notes
Plan Review Notes For Permit 06010664
Permit Number 06010664
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-03 00:00:00DENIED
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION ERQUIRED FOR PLAN REVIEW:
  
 1. MORE INFORMATION IS REQUIRED. THE
 FIRST PAGE APPEARS TO HAVE A RETURN LINE
 TO THE 18" RAISED SHEER WALL, BUT THE
 PIPING SCHEMATIC AND THE EQUIPMENT
 LAYOUT DO NOT SHOW THIS, PLEASE CLARIFY
 THIS.ALSO EQUIPMENT DRAWING LEGEND
 SHOULD INDICATE ON "C" THAT THE 1-1/2"
 HORSE POWER RECIRCULATING PUMP HAS AN
 APPROVED HAIR AND LENT CATCHER.PIPING
 SCHEMATIC SHOULD ALSO INDICATE THE
 1-1/2" VENT LINE FOR THE MAIN DRAIN.
  
 END OF COMMENTS:
  