2006-02-17 00:00:00 | |
| |
| DENIED |
| |
| 1) THE PERMIT APPLICATION SHALL INCLUDE |
| TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| IS RELEVANT. THESE SHOULD INCLUDE THE |
| FLORIDA STATE APPROVAL COVER PAGES, AND |
| THE PRODUCT NOA THAT LISTS THE SYSTEM |
| COMPONENTS/ FASTENER LIST PAGES, THE |
| PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM |
| TO BE USED AND THE GENERAL LIMITATIONS |
| PAGE. ALL CAN BE FOUND ON |
| WWW.FLORIDABUILDING.ORG |
| |
| 2) NOA'S FOR WINDOWS SHALL BE MARKED |
| SHOWING THE TYPE OF WALL AND CONNECTION |
| ALSO TYPE OF FASTENER THAT WIIL BE USED |
| AND TYPE OF GLASS IN WINDOW. THESE ARE |
| ALL NEEDED TO ENSURE THE DESIGN |
| PRESSURES MEET CODE |
| |
| 3) CONTRACTOR'S LICENCE U-16576 IS AN |
| ALUMINUM SPECIALTIES LICENCE AND DOES |
| NOT ALLOW FOR WINDOW AND DOOR |
| INSTALLATION INTO STRUCTURES OTHER THAN |
| PATIO ENCLOSURES. A CONTRACTOR LICENCED |
| TO PERFORM THIS WORK MAY REQUIRE A |
| SEPERATE PERMIT |
| |
| 4) 2 COPIES OF A KEY PLAN WITH DOOR AND |
| WINDOW SIZES CLEARLY MARKED AND A |
| SCHEDULE WITH PANEL SPANS, EDGE DISTANCE |
| OF FASTENERS,TYPE OF FASTENER, TYPE OF |
| CONSTRUCTION, ETC. SHALL ACCOMPANY THE |
| PERMIT APPLICATION TO FACILITATE PLAN |
| REVIEW AND INSPECTION. SEE ATTACHED |
| INFORMATION SHEET AND SCHEDULE |
| |
| 5) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO A |
| PERMIT BEING ISSUED |
| |
| 6) IF A NEW CONRTACTOR IS TO BE USED A |
| CHANGE OF CONTRACTOR FORM SHALL BE |
| FILLED OUT AND NOTORIZED AND A NEW |
| PERMIT APPLICATION MUST BE FILED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |