2006-07-05 00:00:00 | **** UNSAT **** |
| |
| |
| |
| ** |
| 1) NOTE: PLEASE SEE THE ELECTRICAL PAGE |
| CONTAINS "WHITE-OUT" AND HAND DRAWN |
| CHANGES. PLEASE KNOW, IN NO CASE CAN |
| "WHITE OUT" BE USED ON PLANS. HAND DRAWN |
| CHANGES MAY BE DONE BY A DESIGNER OF |
| RECORD, HOWEVER EACH AND EVERY HAND |
| WRITTEN DETAIL OR CHANGED WOULD BE |
| REQUIRED TO BE SIGNED/INITIALED AND |
| DATED. |
| PLEASE REPRINT SHEETS ALONG WITH ANY |
| COMMENTS FROM ANY OTHER TRADES AND SIGN, |
| DATED AND SEAL PLANS. |
| FS 481.221. |
| |
| 2) NOTE: PLEASE SEE BUILDING REVIEW |
| ADJUSTED THE VALUE FOR SCOPE PF WORK, |
| HOWEVER THE FEES WERE NOT PAID. THESE |
| FEES ARE REQUIRED TO BE PAID. |
| FBC ADMIN SECT 108.3 |
| |
| 3) NOTE: ONE SET/COPY OF THE OLD/VOIDED |
| SHEETS WERE NOTSUBMITTED FOR |
| REFERENCE? |
| PLEASE SEE THESE PLANS ARENOWMISSING |
| THE AIC RATING OF THE SERVICE EQUIPMENT. |
| PLEASE REVISE AND INDICATE THIS. |
| 110.9/215.5 |
| |
| 4) NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN DISCONNECT |
| TO THE SUB PANEL. |
| 250.110.250.24B,250.122 |
| THIS WAS NOTED ON PREVIOUS REVIEW TO |
| INCLUDE. |
| |
| **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT THE NEW REVISED SHEETS |
| FOR REVIEW STAMPING. |
| ONE SET OF THE OLD/VOIDED REMOVED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |