Plan Review Notes
Plan Review Notes For Permit 06010507
Permit Number 06010507
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-05 00:00:00**** UNSAT ****
  
  
  
 **
 1) NOTE: PLEASE SEE THE ELECTRICAL PAGE
 CONTAINS "WHITE-OUT" AND HAND DRAWN
 CHANGES. PLEASE KNOW, IN NO CASE CAN
 "WHITE OUT" BE USED ON PLANS. HAND DRAWN
 CHANGES MAY BE DONE BY A DESIGNER OF
 RECORD, HOWEVER EACH AND EVERY HAND
 WRITTEN DETAIL OR CHANGED WOULD BE
 REQUIRED TO BE SIGNED/INITIALED AND
 DATED.
 PLEASE REPRINT SHEETS ALONG WITH ANY
 COMMENTS FROM ANY OTHER TRADES AND SIGN,
 DATED AND SEAL PLANS.
 FS 481.221.
  
 2) NOTE: PLEASE SEE BUILDING REVIEW
 ADJUSTED THE VALUE FOR SCOPE PF WORK,
 HOWEVER THE FEES WERE NOT PAID. THESE
 FEES ARE REQUIRED TO BE PAID.
 FBC ADMIN SECT 108.3
  
 3) NOTE: ONE SET/COPY OF THE OLD/VOIDED
 SHEETS WERE NOTSUBMITTED FOR
 REFERENCE?
 PLEASE SEE THESE PLANS ARENOWMISSING
 THE AIC RATING OF THE SERVICE EQUIPMENT.
 PLEASE REVISE AND INDICATE THIS.
 110.9/215.5
  
 4) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO THE SUB PANEL.
 250.110.250.24B,250.122
 THIS WAS NOTED ON PREVIOUS REVIEW TO
 INCLUDE.
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 FOR REVIEW STAMPING.
 ONE SET OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  