2006-02-09 00:00:00DENIED;
 1.PAN REQUIRED FOR WATER HEATER WITH
 3/4" DRAIN PIPE TO OUTSIDE. SEEFBC-2004
 RESIDENTIAL SEC. P2801.5, P2801.5.1 AND
 P2801.5.2.
 2.SANITARY RISER DIAGRAM, THE WASHER AND
 KITCHEN SINK BRANCH DRAINS ARE REQUIRED
 TO DISCHARGE DOWN STREAM OF THE VENT FOR
 THE 1/2 BATH. FBC-2004 RESIDENTIAL SEC.
 P3108.
 3.AUTOMATIC CLOTHES WASHER CLEANOUT TO
 BE 48" AFF. PLEASE AND NOTE TO RISER
 DIAGRAM.