2006-02-09 00:00:00*** DENIED ***
 1) SENSIBLE BTU'S AND TOTAL BTU'S ON
 MECHANICAL PLANS EQUIP. LIST & MANUAL J
 EQUIP. LIST DO NOT MATCH PLEASE CORRECT.
  
 2) CFM'S ON MANUAL J PER ROOM, AND
 MECHANICAL PLANS LAY OUT PER ROOM DO NOT
 MATCH, (SOME SUPPLY AIR DUCTS APPEAR TO
 BE TO LARGE) PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  