Plan Review Notes For Permit 06010507 |
Permit Number |
06010507 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-09 00:00:00 | *** DENIED *** | | 1) SENSIBLE BTU'S AND TOTAL BTU'S ON | | MECHANICAL PLANS EQUIP. LIST & MANUAL J | | EQUIP. LIST DO NOT MATCH PLEASE CORRECT. | | | | 2) CFM'S ON MANUAL J PER ROOM, AND | | MECHANICAL PLANS LAY OUT PER ROOM DO NOT | | MATCH, (SOME SUPPLY AIR DUCTS APPEAR TO | | BE TO LARGE) PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|